8
MITSUBISHI ELECTRIC AUTOMATION
2.3
Pre Network Connection Procedure
NOTE:
Each Device on the network must be assigned a unique station
number between the values of 0 to 63
1. Set the two Station number switches , Figure 1-1, for a address between
0 and 63. Any number out of the range of 0 to 63 is automatically changed
to 63 by the option unit software.
2. Be sure that the FR-A5ND option unit is snugly inserted into the VFD
and the option unit connector is fully and firmly seated before proceeding.
3. Remove the option data port insert, Figure 2-5 from the VFD cover.
4. Reinstall the VFD cover making sure that option port opening is aligned
with the DeviceNet connector.
5. Connect the DeviceNet thin drop cable to the VFD by inserting the 5-pin
connector through the data port opening, into the DeviceNet standard
socket on the option unit.
Figure 2-5. VFD Data Port
Option Data Port
Inverter Cover