FR-A5ND
DeviceNet
Communications Option Unit
23
The following tables explain how to set each field for Prs.345 & 346.
Reference Table For Pr345
Enter the Sum into PU by hand, if you do not have a DeviceNet Configuration
Tool. In the table above, e.g.1 is the same as default settings, where:
AddrKey = 1010 (Binary) = 10 only,
WDA = 0,
DFM = 0 only,
NodeAddr = 111111 (Binary) = 63,
Sum = 10*4096 + 0*512 + 0*64 + 63*1 = 41023.
Reference Table For Pr346
Please enter the Sum into PU by hand, if you do not have a DeviceNet
Configuration Tool. In the table above, e.g.1 is the same as the default set-
tings, where:
BRKey = 0101 (Binary) = 5 only,
InputAssy = 1 for Instance 71,
OutputAssy = 1 for Instance 21,
BR = 0 for 125 kbps,
Sum = 5*4096 + 1*128 + 1*4 + 0*1 = 20612.
Field
Name
Range
Factor
e.g.1
e.g.2
e.g.3
3 Key
10
4096
10*4096
10*4096
10*4096
2 WDA
0~3
512
0*512
1*512
2*512
1 DFM
0
64
0*64
0*64
0*64
0 Addr
0~63
1
63*1
4*1
10*1
Sum ----
----
----
41023
41476
41994
Field
Name
Range
Factor
e.g.1
e.g.2
e.g.3
3 Key
5
4096
5*4096
5*4096
5*4096
2 Inp
0~6
128
1*128
0*128
6*128
1 Outp
0~6
4
1*4
0*4
6*4
0 BR
0~2
1
0*1
1*1
2*1
Sum ----
----
----
20612
20481
21274