FR-A5ND
DeviceNet
Communications Option Unit
7
Table 2-1. Pin Out Functions
1. Strip the insulation and shielding back 1.5 inches on the free wire end of
the drop cable to expose the four colored signal wires and the silver
shield wire.
2. Strip the insulation back about ¼ inch on the signal wires. And tin each
lead with solder.
3. Tin the end of the shield wire to prevent fraying.
4. Attach the connector to the DeviceNet cable as follow:
a. Using a flathead screwdriver (3.75 mm maximum width), insert the
screwdriver into the upper holes of the connector plug, Figure 2-4, to
open the clamps in the lower holes to allow wires to be inserted.
b. Install the signal wires into the Phoenix Contact connector plug as
shown in Figure 2-4. Be sure to match the wire colors to the correct
pin as shown in Table 2-1.
c. After all wires are properly inserted, turn the holding screws, Figure
2-4 clockwise to securely clamp the wires. When properly tightened,
wires should not be able to be pulled out
.
o
N
n
i
P
r
o
l
o
C
l
a
n
g
i
S