- 42 -
[2-9 Example System with an MA and an ME Remote Controller ]
GB
HWE14080
2-9
Example System with an MA and an ME Remote Controller
2-9-1
System with a Connection of System Controller to Centralized Control
Transmission Line
(1) Sample control wiring
(2) Cautions
1) Be sure to connect a system controller.
2) ME remote controller and MA remote controller cannot
both be connected to the same group of indoor units.
3) Assign to the indoor units connected to the MA remote
controller addresses that are smaller than those of the in-
door units that are connected to the ME remote control-
ler.
4) No more than 2 ME remote controllers can be connected
to a group of indoor units.
5) No more than 2 MA remote controllers can be connected
to a group of indoor units.
6) Do not connect the terminal blocks (TB5) on the indoor
units that are connected to different outdoor units with
each other.
7) Replace the power jumper connector of the control board
from CN41 to CN40 on only one of the outdoor units.
8) Provide an electrical path to ground for the S terminal on
the terminal block for centralized control on only one of
the outdoor units.
9) A transmission booster must be connected to a system
in which the total number of connected indoor units ex-
ceeds 20.
10) A transmission booster is required in a system to which
more than 16 indoor including one or more indoor units
of the 72 model or above are connected.
Refer to the DATABOOK for further information about
how many booster units are required for a given system.
11) When a power supply unit is connected to the transmis-
sion line for centralized control, leave the power jumper
connector on CN41 as it is (factory setting).
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Same as 2-7-3
2) Transmission line for centralized control
Same as 2-7-4
3) MA remote controller wiring
Same as 2-7-1
4) M-NET remote controller wiring
Same as 2-7-1
5) Maximum line distance via outdoor unit
(1.25 mm
2
[AWG16] min. )
Same as 2-7-4
IC
TB5 TB15
1 2
01
IC
TB5 TB15
1 2
02
IC
TB5 TB15
1 2
06
106
IC
TB5 TB15
1 2
05
A B
MA
A B
RC
A B
MA
IC
TB5
1 2
TB15
IC
TB5 TB15
1 2
04
03
104
A B
RC
L11 L12
L21 L22
TB3
TB7
S
TB3
TB7
S
TB3
TB7
M1 M2
M1 M2
M1 M2
M1 M2
M1 M2
M1 M2
S
OC
TB3
TB7
S
54
OS1
TB3
TB7
S
55
OS2
TB3
TB7
M1 M2
M1 M2
M1 M2
M1 M2
M1 M2
M1 M2
S
56
L31
A B S
L32
S
M1 M2
S
M1 M2
S
M1 M2
SW5-1 OFF ON
Leave the male
connector on
CN41 as it is.
SW5-1 OFF ON
Leave the male
connector on
CN41 as it is.
OC
OS1
OS2
51
52
53
Move the male connector
from CN41 to CN40.
SW5-1 OFF ON
Group
Group
Group
Group
SW5-1 OFF ON
Leave the male
connector on
CN41 as it is.
SW5-1 OFF ON
Leave the male
connector on
CN41 as it is.
SW5-1 OFF ON
Leave the male
connector on
CN41 as it is.
Note1
System controller
Note1 When only the LM adapter is connected,
leave SW5-1 to OFF (as it is).
Note2 LM adapters require the power supply
capacity of single-phase AC 208/230V.
To be connected
To be left
unconnected
To be left
unconnected
To be left
unconnected
To be left
unconnected
To be left
unconnected
S
M1 M2
S
M1 M2
S
M1 M2
Содержание R410A
Страница 1: ......
Страница 11: ... 2 HWE14080 GB ...
Страница 25: ... 16 HWE14080 GB ...
Страница 38: ... 2 6 System Connection Example 29 HWE14080 GB 2 Restrictions ...
Страница 57: ... 2 10 Restrictions on Refrigerant Pipes 48 HWE14080 GB ...
Страница 59: ... 50 HWE14080 GB ...
Страница 71: ... 62 HWE14080 GB ...
Страница 95: ... 86 HWE14080 GB ...
Страница 121: ... 5 3 Operation Flowcharts 112 HWE14080 GB ...
Страница 123: ... 114 HWE14080 GB ...
Страница 159: ... 150 HWE14080 GB ...
Страница 243: ... 7 8 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14080 GB ...
Страница 309: ... 300 HWE14080 GB ...
Страница 346: ......