[7-6 Error Code Definitions and Solutions: Codes [5000 - 5999] ]
- 204 -
HWE14080
GB
7-6-17
Error Codes [5305, 5306] Detail Code 134
1. Error
code
definition
RPM error before start up (Detail code 134)
2. Error definition and error detection method
The fan RPM will not drop to the set RPM.
3. Cause, check method and remedy
For inverter-related error codes, refer to the following page(s).
[8-9 Troubleshooting Inverter Problems (TLMU)](page 264)
[8-10 Troubleshooting Inverter Problems (YLMU)](page 276)
7-6-18
Error Code [5401]
1. Error
Code
Humidity sensor fault
2. Error definition and error detection method
A short-circuit or an open-circuit of the humidity sensor is detected during operation.
3. Cause, check method and remedy
Cause
Check method and remedy
(1)
Outdoor factors
Check that there is no wind (gust or strong wind).
(2)
Fan board failure
Refer to the following page(s).
(TLMU)
[8-9-8 Checking the Fan Inverter for Damage at No Load](page 269)
[8-9-9 Checking the Fan Inverter for Damage with Load](page 270)
(YLMU)
[8-10-8 Checking the Fan Inverter for Damage at No Load](page 280)
[8-10-9 Checking the Fan Inverter for Damage with Load](page 281)
(3)
Fan motor error
Refer to the following page(s).
(TLMU)
[8-9-6 Checking the Fan Motor for Ground Fault and Coil Resistance Problems](page 268)
(YLMU)
[8-10-6 Checking the Fan Motor for Ground Fault and Coil Resistance Problems](page
279)
5401
Cause
Check method and remedy
(1)
Connector contact failure (CN30) (Loose con-
nector)
1)
Check the connector for proper contact.
Reconnect the connector, and operate the unit to check for
proper operation.
(2)
Broken or partially broken humidity sensor wire 2)
Check for broken humidity sensor wire.
(3)
Humidity sensor fault
3)
Check the output voltage across No. 1 and No. 3 pins of
connector CN30 with the connector being connected to the
indoor unit control board.
30% : 1.25V
40% : 1.52V
50% : 1.88V
60% : 2.19V
70% : 2.48V
80% : 2.79V
(4)
Indoor unit control board (detection circuit) fault 4)
If the above items check out okay, replace the indoor unit
control board.
Содержание R410A
Страница 1: ......
Страница 11: ... 2 HWE14080 GB ...
Страница 25: ... 16 HWE14080 GB ...
Страница 38: ... 2 6 System Connection Example 29 HWE14080 GB 2 Restrictions ...
Страница 57: ... 2 10 Restrictions on Refrigerant Pipes 48 HWE14080 GB ...
Страница 59: ... 50 HWE14080 GB ...
Страница 71: ... 62 HWE14080 GB ...
Страница 95: ... 86 HWE14080 GB ...
Страница 121: ... 5 3 Operation Flowcharts 112 HWE14080 GB ...
Страница 123: ... 114 HWE14080 GB ...
Страница 159: ... 150 HWE14080 GB ...
Страница 243: ... 7 8 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14080 GB ...
Страница 309: ... 300 HWE14080 GB ...
Страница 346: ......