[8-10 Troubleshooting Inverter Problems (YLMU) ]
- 279 -
HWE14080
GB
8
Tr
oubles
hoot
ing Ba
se
d
o
n
Obs
erv
ed Sympt
o
ms
8-10-5
Checking the Inverter for Damage during Compressor Operation
8-10-6
Checking the Fan Motor for Ground Fault and Coil Resistance Problems
8-10-7
Checking the Fan Board Error Detection Circuit at No Load
Items to be checked
Phenomena
Remedy
Put the outdoor unit into operation.
Check the inverter output voltage af-
ter the inverter output frequency has
stabilized.
1)
Overcurrent-related problems occur im-
mediately after compressor startup.
Error code : 4250
Detail code : 101, 102, 106, 107
a.
Check items 8-10-2 through 8-
10-4 for problems.
b.
Check that high and low pres-
sures are balanced.
c.
Check that no liquid refrigerant
is present in the compressor.
ĺ
Go to "d." when the problem
persists after compressor start-
up was repeated several times.
If normal operation is restored,
check the belt heater for prob-
lems.
d.
Check that there is a pressure
difference between high and
low pressures after compres-
sor startup.
ĺ
Check the high pressure with
LED monitor for changes.
Replace the compressor if
there is no pressure difference.
(the compressor may be
locked.)
2)
There is a voltage imbalance between
the wires after the inverter output voltage
is stabilized.
Greater than the larger of the following
values: imbalance of 5% or 5V
Replace the INV board if there is a
voltage imbalance.
Check the belt heater for problems if
there is no voltage imbalance.
ĺ
When the error occurred, liquid
refrigerant may have been present
in the compressor.
Items to be checked
Phenomena
Remedy
Remove fan motor winding. Check
insulation resistance and coil resis-
tance.
1)
Fan motor insulation failure.
If < 1 M
ȍ
, Defect.
Change fan motor.
2)
Fan motor wire failure.
Normal coil resistance is a few ohms.
(Changes with temperature)
Change fan motor.
Items to be checked
Phenomena
Remedy
(1)
Turn off breaker.
*Turn power off without fail.
1)
Electrical current over load error.
Check code: 4255, 4256
Detail code: 101, 104
Change fan board.
(2)
Remove fan board CNINV
and CNSNR connectors.
2)
Logic error
Check code: 4225, 4256
Detail code:111
Change fan board.
(3)
Turn on breaker.
3)
Position error on start up
Check code: 5305, 5306
Detail code: 132
Normal
*After checking, return connector
CNINV & CNSNR.
(4)
Operate unit.
Содержание R410A
Страница 1: ......
Страница 11: ... 2 HWE14080 GB ...
Страница 25: ... 16 HWE14080 GB ...
Страница 38: ... 2 6 System Connection Example 29 HWE14080 GB 2 Restrictions ...
Страница 57: ... 2 10 Restrictions on Refrigerant Pipes 48 HWE14080 GB ...
Страница 59: ... 50 HWE14080 GB ...
Страница 71: ... 62 HWE14080 GB ...
Страница 95: ... 86 HWE14080 GB ...
Страница 121: ... 5 3 Operation Flowcharts 112 HWE14080 GB ...
Страница 123: ... 114 HWE14080 GB ...
Страница 159: ... 150 HWE14080 GB ...
Страница 243: ... 7 8 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14080 GB ...
Страница 309: ... 300 HWE14080 GB ...
Страница 346: ......