[7-5 Error Code Definitions and Solutions: Codes [4000 - 4999] ]
- 181 -
HWE14080
GB
7
Tro
ubles
hoot
in
g Us
in
g
Er
ror Codes
7-5-17
Error Codes [4220, 4225, 4226] Detail Code 131
1. Error
code
definition
Low bus voltage at startup (Detail code 131)
2. Error definition and error detection method
When Vdc
160 V is detected just before the inverter operation.
3. Cause, check method and remedy
(1) Inverter main circuit failure
Same as detail code 108 of 4220 error
For inverter-related error codes, refer to the following page(s).
[8-9 Troubleshooting Inverter Problems (TLMU)](page 264)
[8-10 Troubleshooting Inverter Problems (YLMU)](page 276)
7-5-18
Error Code [4230] (TLMU)
1. Error
code
definition
Heatsink overheat protection
2. Error definition and error detection method
When the heat sink temperature (THHS) remains at or above TOH is detected.
Refer to the relevant pages for the details of model names and the specified values. [7-1-1 Inverter Protection Level Ta-
ble](page 155)
3. Cause, check method and remedy
For inverter-related error codes, refer to the following page(s). [8-9 Troubleshooting Inverter Problems (TLMU)](page 264)
Model
TOH
INV24
100°C [212°F]
INV25
90°C [194°F]
Cause
Check method and remedy
(1)
Fan board failure
Refer to the following page(s).
[8-9-7 Checking the Fan Board Error Detection Circuit at No Load](page 268)
[8-9-8 Checking the Fan Inverter for Damage at No Load](page 269)
[8-9-9 Checking the Fan Inverter for Damage with Load](page 270)
(2)
Outdoor unit fan failure
Check the outdoor unit fan operation.
If any problem is found with the fan operation, check the fan motor.
Refer to the following page(s). [8-9-6 Checking the Fan Motor for Ground Fault
and Coil Resistance Problems](page 268)
(3)
Air passage blockage
Check that the heat sink cooling air passage is not blocked
(4)
THHS failure
P72, P96, P120, P144 models
1)
Check for proper installation of the INV board IGBT. (Check for proper installa-
tion of the IGBT heatsink.)
2)
Check for proper installation of the INV board IGBT.
ĺ
If an abnormal value appears, replace the INV board.
P168 model
3)
Check the THHS sensor reading on the LED monitor.
ĺ
If an abnormal value appears, check the sensor resistance, and replace the
sensor as necessary.
Содержание R410A
Страница 1: ......
Страница 11: ... 2 HWE14080 GB ...
Страница 25: ... 16 HWE14080 GB ...
Страница 38: ... 2 6 System Connection Example 29 HWE14080 GB 2 Restrictions ...
Страница 57: ... 2 10 Restrictions on Refrigerant Pipes 48 HWE14080 GB ...
Страница 59: ... 50 HWE14080 GB ...
Страница 71: ... 62 HWE14080 GB ...
Страница 95: ... 86 HWE14080 GB ...
Страница 121: ... 5 3 Operation Flowcharts 112 HWE14080 GB ...
Страница 123: ... 114 HWE14080 GB ...
Страница 159: ... 150 HWE14080 GB ...
Страница 243: ... 7 8 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14080 GB ...
Страница 309: ... 300 HWE14080 GB ...
Страница 346: ......