[5-1 Dipswitch Functions and Factory Settings ]
- 93 -
HWE14080
GB
5
Control
(2) ME remote controller (PAR-F27MEA-US)
Set the address of the remote controller with the rotary switch.
To set addresses, use a precision slotted screw driver [2.0 mm [0.08 in] (w)], and do not apply than 19.6N.
The use of any other tool or applying too much load may damage the switch.
012
3
45
67
8
9
012
3
45
67
8
9
012
3
45
67
8
9
012
3
45
67
8
9
10's digit 1's digit
(left)
(right)
Remote controller unit
Rotary switch
Example: In case of address 108
Address setting range
Setting method
Main remote controller
101-150
Add 100 to the smallest address of all the indoor units in the
same group.
Sub remote controller
151-200
Add 150 to the smallest address of all the indoor units in the
same group.
Setting of rotary switch
Address No.
01-99
*1
101-199 with the 100's digit automatically being set to 1
*2
00
200
*1. At factory shipment, the rotary switch is set to 01.
*2. The address range that can be set with the ME remote controller is between 101 and 200. When the dials are set to
a number between 01 and 99, the 100's digit is automatically set to [1]. When the dials are set to 00, the 100's digit is
automatically set to [2].
Содержание R410A
Страница 1: ......
Страница 11: ... 2 HWE14080 GB ...
Страница 25: ... 16 HWE14080 GB ...
Страница 38: ... 2 6 System Connection Example 29 HWE14080 GB 2 Restrictions ...
Страница 57: ... 2 10 Restrictions on Refrigerant Pipes 48 HWE14080 GB ...
Страница 59: ... 50 HWE14080 GB ...
Страница 71: ... 62 HWE14080 GB ...
Страница 95: ... 86 HWE14080 GB ...
Страница 121: ... 5 3 Operation Flowcharts 112 HWE14080 GB ...
Страница 123: ... 114 HWE14080 GB ...
Страница 159: ... 150 HWE14080 GB ...
Страница 243: ... 7 8 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14080 GB ...
Страница 309: ... 300 HWE14080 GB ...
Страница 346: ......