[2-4 M-NET Address Settings ]
- 23 -
HWE14080
GB
2
Re
st
ri
ct
io
n
s
2-4-5
Start/Stop Control of Indoor Units
Each indoor unit (or group of indoor units) can be controlled individually by setting SW 1-9 and 1-10.
*1. Do not cut off power to the outdoor unit. Cutting off the power supply to the outdoor unit will cut off the power supply to the
belt heater and may cause the compressor to malfunction when the unit is put back into operation.
*2. Not applicable to units with a built-in drain pump or humidifier.
*3. Models with a built-in drain pump cannot be turned on/off by the plug individually. All the units in the same refrigerant cir-
cuits will be turned on or off by the plug.
*4. Requires that the dipswitch settings for all the units in the group be made.
*5. When using the free contact on the indoor units, set SW1-9 and SW1-10 to ON. With these settings made, the power start-
stop function becomes disabled. To use the auto recovery function after power failure while these settings are made, set
SW1-5 to ON.
2-4-6
Miscellaneous Settings
Cooling-only setting for the indoor unit: Cooling only model (Factory setting: SW3-1 "OFF.")
When using indoor unit as a cooling-only unit, set SW3-1 to ON.
Function
Operation of the indoor unit when the operation is resumed after the unit was
stopped
Setting (SW1)
*4 *5
9
10
Power ON/OFF by
the plug
*1,*2,*3
Indoor unit will go into operation regardless of its operation status before power
off (power failure). (In approx. 5 minutes)
OFF
ON
Automatic restoration
after power failure
Indoor unit will go into operation if it was in operation when the power was
turned off (or cut off due to power failure). (In approx. 5 minutes)
ON
OFF
Indoor unit will remain stopped regardless of its operation status before power
off (power failure).
OFF
OFF
Содержание R410A
Страница 1: ......
Страница 11: ... 2 HWE14080 GB ...
Страница 25: ... 16 HWE14080 GB ...
Страница 38: ... 2 6 System Connection Example 29 HWE14080 GB 2 Restrictions ...
Страница 57: ... 2 10 Restrictions on Refrigerant Pipes 48 HWE14080 GB ...
Страница 59: ... 50 HWE14080 GB ...
Страница 71: ... 62 HWE14080 GB ...
Страница 95: ... 86 HWE14080 GB ...
Страница 121: ... 5 3 Operation Flowcharts 112 HWE14080 GB ...
Страница 123: ... 114 HWE14080 GB ...
Страница 159: ... 150 HWE14080 GB ...
Страница 243: ... 7 8 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14080 GB ...
Страница 309: ... 300 HWE14080 GB ...
Страница 346: ......