[7-5 Error Code Definitions and Solutions: Codes [4000 - 4999] ]
- 190 -
HWE14080
GB
7-5-28
Error Code [4260] (TLMU)
1. Error
code
definition
Heatsink overheat protection at startup
2. Error definition and error detection method
The heatsink temperature (THHS) remains at or above TOH for 10 minutes or more at inverter startup.
Refer to the relevant pages for the details of model names and the specified values. [7-1-1 Inverter Protection Level Ta-
ble](page 155)
3. Cause, check method and remedy
Same as 4230 error
7-5-29
Error Code [4260] (YLMU)
1. Error
code
definition
Heatsink overheat protection at startup
2. Error definition and error detection method
The heatsink temperature (THHS) remains at or above 105°C [221°F] for 10 minutes or more at inverter startup.
3. Cause, check method and remedy
Same as 4230 error
Model
TOH
INV24
100°C [212°F]
INV25
90°C [194°F]
Содержание R410A