[7-7 Error Code Definitions and Solutions: Codes [6000 - 6999] ]
- 207 -
HWE14080
GB
7
Tro
ubles
hoot
in
g Us
in
g
Er
ror Codes
7-7-3
Error Code [6600]
1. Error
code
definition
Address overlap
2. Error definition and error detection method
An error in which signals from more than one indoor units with the same address are received
The address and attribute that appear on the remote controller indicate the controller that detected the error.
3. Cause, check method and remedy
7-7-4
Error Code [6601]
1. Error
code
definition
Polarity setting error
2. Error definition and error detection method
The error detected when transmission processor cannot distinguish the polarities of the M-NET transmission line.
3. Cause, check method and remedy
Cause
Check method and remedy
(1)
Two or more of the following have the same address:
Outdoor units, indoor units, LOSSNAY units, control-
lers such as ME remote controllers.
<Example>
6600 "01" appears on the remote controller
Unit #01 detected the error.
Two or more units in the system have 01 as their ad-
dress.
Find the unit that has the same address as that of the error
source.
Once the unit is found, correct the address.
Then, turn off the outdoor units, indoor units, and
LOSSNAY units, keep them all turned off for at least
five minutes, and turn them back on.
When air conditioning units are operating normally despite
the address overlap error
Check the transmission wave shape and noise on the
transmission line.
See the section "Investigation of Transmission Wave
Shape/Noise."
(2)
Signals are distorted by the noise on the transmission
line.
Cause
Check method and remedy
(1)
No voltage is applied to the M-NET transmission line
that AE-200A/AE-50A/EW-50A/EB-50GU/AG-150A/
GB-50ADA/GB-24A, PAC-YG50ECA, BAC-HD150
is connected to.
Check if power is supplied to the M-NET transmission
line of the AE-200A/AE-50A/EW-50A/EB-50GU/AG-
150A/GB-50ADA/GB-24A, PAC-YG50ECA, BAC-
HD150, and correct any problem found.
(2)
M-NET transmission line to which AE-200A/AE-50A/
EW-50A/EB-50GU/AG-150A/GB-50ADA/GB-24A,
PAC-YG50ECA, BAC-HD150 is connected is short-
circuited.
(3)
When two or more power supplies are connected to
the M-NET
Содержание R410A
Страница 1: ......
Страница 11: ... 2 HWE14080 GB ...
Страница 25: ... 16 HWE14080 GB ...
Страница 38: ... 2 6 System Connection Example 29 HWE14080 GB 2 Restrictions ...
Страница 57: ... 2 10 Restrictions on Refrigerant Pipes 48 HWE14080 GB ...
Страница 59: ... 50 HWE14080 GB ...
Страница 71: ... 62 HWE14080 GB ...
Страница 95: ... 86 HWE14080 GB ...
Страница 121: ... 5 3 Operation Flowcharts 112 HWE14080 GB ...
Страница 123: ... 114 HWE14080 GB ...
Страница 159: ... 150 HWE14080 GB ...
Страница 243: ... 7 8 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14080 GB ...
Страница 309: ... 300 HWE14080 GB ...
Страница 346: ......