[2-5 Demand Control Overview ]
- 27 -
HWE14080
GB
2
Re
st
ri
ct
io
n
s
2) When SW6-8 on one outdoor unit in one refrigerant circuit system is set to ON (4 levels of on-DEMAND)
(*3)
*3. Input the order to CN3D on the outdoor unit whose SW6-8 is set to ON.
3) When SW6-8 on the two outdoor units in one refrigerant circuit system is set to ON (8 levels of on-DEMAND)
(*4, *5)
*4. Input the order to CN3D on the outdoor unit whose SW6-8 is set to ON.
*5. CN3D of No. 1, 2, 3 can be selected arbitrary with the outdoor unit whose SW6-8 is set to ON.
4) When SW6-8 on the all outdoor units in one refrigerant circuit system is set to ON (12 levels of on-DEMAND)
(*4)
*3. Input the order to CN3D on the outdoor unit whose SW6-8 is set to ON.
*4. CN3D of No. 1, 2, 3 can be selected arbitrary with the outdoor unit whose SW6-8 is set to ON.
CN3D 1-2P
CN3D 1-3P
Open
Short-circuit
Open
100% (No DEMAND)
75%
Short-circuit
0% (Compressor OFF)
50%
8 levels of on-DEMAND
No.2 CN3D
1-2P
Open
Short-circuit
No.1 CN3D
1-2P
1-3P
Open
Short-circuit
Open
Short-circuit
Open
Open
100%
50%
88%
75%
Short-circuit
50%
0%
38%
25%
Short-circuit
Open
88%
38%
75%
63%
Short-circuit
75%
25%
63%
50%
12 levels
of on-DE-
MAND
No.2 CN3D
1-2P
Open
1-3P
Open
Short-circuit
No.3 CN3D
1-2P
Open
Short-circuit
Open
Short-circuit
No.1
CN3D
1-2P
1-3P
Open
Short-
circuit
Open
Short-
circuit
Open
Short-
circuit
Open
Short-
circuit
Open
Open
100%
67%
92%
84%
67%
34%
59%
50%
Short-
circuit
67%
34%
59%
50%
34%
0%
25%
17%
Short-circuit
Open
92%
59%
84%
75%
59%
25%
50%
42%
Short-
circuit
84%
50%
75%
67%
50%
17%
42%
34%
12 levels
of on-DE-
MAND
No.2 CN3D
1-2P
Short-circuit
1-3P
Open
Short-circuit
No.3 CN3D
1-2P
Open
Short-circuit
Open
Short-circuit
No.1
CN3D
1-2P
1-3P
Open
Short-
circuit
Open
Short-
circuit
Open
Short-
circuit
Open
Short-
circuit
Open
Open
92%
59%
84%
75%
84%
50%
75%
67%
Short-
circuit
59%
25%
50%
42%
50%
17%
42%
34%
Short-circuit
Open
84%
50%
75%
67%
75%
42%
67%
59%
Short-
circuit
75%
42%
67%
59%
67%
34%
59%
50%
If the step listed as the wrong example above is taken, thermo may go off.
The percentage of the demand listed in the table above is an approximate value based on the
compressor volume and does not necessarily correspond with the capacity.
When this function is enabled, the night mode cannot be enabled.
(Wrong)
(Correct)
100%
100%
0%
75%
50%
50%
Demand control
steps
Note the following steps to be taken when using the STEP DEMAND
(Example) When switching from 100% to 50%
Содержание R410A
Страница 1: ......
Страница 11: ... 2 HWE14080 GB ...
Страница 25: ... 16 HWE14080 GB ...
Страница 38: ... 2 6 System Connection Example 29 HWE14080 GB 2 Restrictions ...
Страница 57: ... 2 10 Restrictions on Refrigerant Pipes 48 HWE14080 GB ...
Страница 59: ... 50 HWE14080 GB ...
Страница 71: ... 62 HWE14080 GB ...
Страница 95: ... 86 HWE14080 GB ...
Страница 121: ... 5 3 Operation Flowcharts 112 HWE14080 GB ...
Страница 123: ... 114 HWE14080 GB ...
Страница 159: ... 150 HWE14080 GB ...
Страница 243: ... 7 8 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14080 GB ...
Страница 309: ... 300 HWE14080 GB ...
Страница 346: ......