[7-1 Error Code and Preliminary Error Code Lists ]
- 155 -
HWE14080
GB
7
Tro
ubles
hoot
in
g Us
in
g
Er
ror Codes
7-1-1
Inverter Protection Level Table
INV board
Outdoor units
Overload
protection
Imax (Arms)
Current effective
value error
(Arms)
Current peak value
error (Apeak)
Temperature
protection TOL
(°C)
INV24
PUHY-P72TLMU
26
31
53
95
PUHY-P96TLMU
26
31
53
95
PUHY-P120TLMU
42
50
82
95
PUHY-P144TLMU
42
50
82
95
INV25
PUHY-P168TLMU
53
64
106
80
INV20Y
PUHY-P72YLMU
14
17
28
100
PUHY-P96YLMU
14
17
28
100
PUHY-P120YLMU
22
26
44
100
PUHY-P144YLMU
22
26
44
100
PUHY-P168YLMU
27
33
56
100