- 47 -
(2)-4 Installation method
•
Using the anchoring holes shown below, fi rmly bolt the unit to the base.
[Fig. IV. 2. (2). 1]
Bases
•
Be sure to install unit in a place strong enough to withstand its weight. If the base is unstable, reinforce with a con-
crete base.
•
The unit must be anchored on a level surface. Use a level to check after installation.
•
If the unit is installed near a room where noise is a problem, using an anti-vibration stand on the base of the unit is
recommended.
(A) 4-ø14 (Anchoring hole)
(B) (Top view)
(A)
(B)
205
300
450
500
525
Unit : mm
(2)-3-2 PWFY-P100, 200VM-E-AU
X
289
277
Model
PWFY-P100VM-E-AU
PWFY-P200VM-E-AU
Z
103
99
Y
346
347
205
13
X
Y
800
500
525
300
450
Z
47
Unit : mm