- 48 -
(3) Refrigerant pipe and drain pipe specifi cations
(3)-1 Refrigerant pipe and drain pipe specifi cations
(3)-2 Refrigerant pipe, drain pipe and fi lling port
Model
Gas
Liquid
Drain
Insulating material's thickness
PWFY-P100VM-E-BU
ø15.88
ø9.52
PWFY-P100VM-E-AU
ø15.88
ø9.52
ø32
More than 10 mm
PWFY-P200VM-E-AU
ø19.05
ø9.52
To avoid dew drops, provide suffi cient antisweating and insulating work to the refrigerant and drain pipes.
When using commercially available refrigerant pipes, be sure to wind commercially available insulating material (with a
heat-resisting temperature of more than 100 °C and thickness given below) onto both liquid and gas pipes.
Be also sure to wind commercially available insulating material (with a form polyethylene’s specifi c gravity of 0.03 and
thickness given below) onto all pipes which pass through rooms.
1) Select the thickness of insulating material by pipe size.
2) If the unit is used on the highest story of a building and under conditions of high temperature and humidity, it is
necessary to use pipe size and insulating material’s thickness more than those given in the table above.
3) If there are customer’s specifi cations, simply follow them.
(A) Refrigerant piping (gas)
(B) Refrigerant piping (liquid)
(C) Water inlet
(D) Water outlet
(E) Drain outlet
*1: PWFY-P100, 200VM-E-AU
(D)
(A)
(B)
(C)
(E)
480
100
191
54
102
114
134
184 (206*1)
Unit : mm
Unit : mm