- 6 -
2. External Dimensions
(1) PWFY-P100VM-E-BU
Piping space
(right side)
Fig. A
Service space
(front side)
T
op view
300
400
600
ø
27 Knockout hole
<Hole for external wiring output>
Drain (R1 screw)
Control box
W
ater outlet
(RC3/4 screw)
ø
27 Knockout hole
<Hole for external wiring input>
ø
27 Knockout hole
<Hole for power supply>
ø
27 Knockout hole
<Hole for control wiring>
Service panel
T
op view
Right side view
Front view
2X2-
ø
14 Hole
Connection pipe of outdoor unit
(Liquid)
ø
15.88 <Brazed>
ø
9.52 <Brazed>
Connection pipe of outdoor unit
(Gas)
W
ater inlet
(R3/4 screw)
525
(Mounting pitch)
(Mounting pitch)
205
800
300
450
500
55
35
35
91
91
134
480
46
60
140
100
191
80
165
102
54
184
11
4
Note 1.Ensure no rain water or debris can enter the unit through any gaps around
wiring or piping.
2.Ensure adequate service space is right around the unit, according to Fig
A.
3.Please always make water circulate or add the brine to the circulation water
when the ambient temperature becomes 0
°C
or less.
4.The unit is not designed for outside installations.
5.Install the unit in an environment where the wet bulb
T
emp.
will not exceed 32degC.
6.Please always make water circulate or pull out the circulation
water completely when not using it.
7.The water circuit must use the closed circuit.
8.Please don't use the steel material for the water piping material.
9.Connect the strainer which is put as accessory to water inlet pipe.
<Accessories>
●Y
-type strainer (RC3/4)
··························
1pc.
●Heat Insulation material
·························
1pc.
●Connector set
········································
2set
<Unit:mm>