- 68 -
2. Dip switch functions
Switch
Function
Function according to switch setting
Switch setting timing
OFF
ON
SW1
1
T
Operation after power recovery *1
Operation after power recovery
H0 thermistor selection
Water inlet thermistor TH6
Water outlet thermistor TH8
Before power on
Before power on
Before power on
2
-
-
-
-
3
Remains stopped
Depends on the SW1-3 setting
Auto recovery (to the status
before power failure)
Forced to operate
*1 Valid only when SW1-4 is set to OFF
4
5
-
-
-
-
6
-
-
-
-
6
-
-
-
-
7
Test-run mode
OFF
ON
Any time
8
Error history deleted
Normal
Deleted
Any time
Interlocked operation with the
pump
Effective
Ineffective
Any time
9
Effective only when SW1-7 is
set to ON and only on the HEX
models.
Heating
Cooling
Any time
10
SW2
1-10
For self-diagnosis/operation
monitoring
-
-
Any time
SW3
1
Capacity setting (HEX unit only) 4HP
8HP ( HEX unit only)
Before power on
2
Service LED display selection
Display in Centigrade
Display in Fahrenheit
Any time
3
-
-
-
-
4
-
-
-
-
5
Cumulative compressor opera-
tion time is deleted.
Normal
Deleted
Any time
6
7
-
-
-
-
8
-
-
-
-
9
-
-
-
-
10
-
-
-
-
SW4
1
2
3
Use to change pr
Do not change from factory setting.
Do not change from factory setting.
eset tempera-
ture range for the Heating ECO
mode.
Booster : Ineffective
HEX : Ineffective
Booster : 30°C to 45°C
HEX : 30°C to 45°C
Before power on
4
Use to change pr
Interlocked pump switching
Excludes stoppage
Thermo-ON only
Any time
eset tempera-
ture range for the Anti-freeze
mode.
BU : Ineffective
WH : Ineffective
BU : 10°C to 45°C
WH : 10°C to 45°C
Before power on
5
-
-
-
-
7
-
-
-
-
8
-
-
-
-
9
-
-
-
-
10
-
-
-
-
SW5
1
Error detection enabled
Enabling/disabling ACCT sensor
error detection
Error detection disable
(No load operation is possible)
Any time
2
-
-
-
-
3
-
-
-
-
4
-
-
-
-