- 1 -
<PWFY-P100,200VM-E-AU>
General Equipment Descriptions
I
1. Unit confi guration table
Model
PWFY-P100VM-E-BU
PWFY-P100VM-E-AU
PWFY-P200VM-E-AU
Outdoor unit
PURY-(E)P•Y(S)JM-A(1)(-BS) / PQRY-P•Y(S)HM-A
PUHY-(E)P•Y(S)JM-A(1)(-BS) / PUHY-HP•Y(S)HM-A(-BS) / PQHY-P•Y(S)HM-A
PURY-(E)P•Y(S)JM-A(1)(-BS) / PQRY-P•Y(S)HM-A
Connection
BC controller
BC controller: CMB-P104,105,106,108,1010,1013,1016V-G1
Main BC controller: CMB-P108,1010,1013,1016V-GA1 / CMB-P1016V-HA1
Sub BC controller: CMB-P104,108V-GB1 / CMB-P1016V-HB1
WCB
CMB-PW202V-J
2. Operable temperature range
<PWFY-P100VM-E-BU>
Only PWFY
PWFY with
standard indoor unit
Only standard
indoor units
Heating
Inlet water temperature R2/WR2 series
10 to 70ºC
10 to 70ºC
–
Outdoor temperature
R2 series
-20 to 32ºCWB
-20 to 32ºCWB
-20 to 15.5ºCWB
Circulating water
temperature WR2 series
10 to 45ºC
10 to 45ºC
10 to 45ºC
<PWFY-P100,200VM-E-AU>
Only PWFY
PWFY with standard indoor units
Cooling
Heating
Cooling
Heating
Inlet water temperature
R2/WR2 series
10 to 35ºC
10 to 40ºC
10 to 35ºC
10 to 40ºC
Y/HP/WY series
10 to 35ºC
10 to 40ºC
10 to 35ºC
10 to 40ºC
Outdoor temperature
R2 series
-5 to 46ºCDB
-20 to 32ºCWB
-5 to 46ºCDB
-20 to 32ºCWB
Y series
-5 to 46ºCDB
-20 to 15.5ºCWB
-5 to 46ºCDB
-20 to 15.5ºCWB
HP series
-5 to 43ºCDB
-25 to 15.5ºCWB
-5 to 43ºCDB
-25 to 15.5ºCWB
Circulating water
temperature
WR2 series
10 to 45ºC
10 to 45ºC
10 to 45ºC
10 to 45ºC
WYseries
10 to 45ºC
10 to 45ºC
10 to 45ºC
10 to 45ºC
Only standard indoor units
Cooling
Heating
Outdoor temperature
R2 series
-5 to 46ºCDB
-20 to 15.5ºCWB
Y series
-5 to 46ºCDB
-20 to 15.5ºCWB
HP series
-5 to 43ºCDB
-25 to 15.5ºCWB
Circulating water
temperature
WR2 series
10 to 45ºC
10 to 45ºC
WYseries
10 to 45ºC
10 to 45ºC
3. Connectable outdoor unit/heat source unit capacity range
<PWFY-P100VM-E-BU>
Only PWFY
PWFY with
standard indoor unit
Only standard
indoor units
R2/WR2 series
50 to 100%
50 to 150%
*1
50 to 150%
*1
Only PWFY
PWFY with
standard indoor unit
Only standard
indoor units
R2/WR2 series
50 to 100%
50 to 150%
*1
50 to 150%
*1
Y/HP/WY series
50 to 100%
50 to 130%
50 to 130%
<BC controller>
Connectable unit
CMB-P104/P105/106/107/1010/
1013/1016V-G1
PURY-(E)P200-350YJM-A(-BS)
PQRY-P200-300YHM-A
CMB-P108/1010/1013/1016V-GA1
PURY-(E)P200-650Y(S)JM-A(1)(-BS)
PQRY-P200-600Y(S)HM-A
CMB-P1016V-HA1
PURY-(E)P700-900YSJM-A(1)(-BS)
CMB-P104/108V-GB1, CMB-P1016V-HB1
CMB-P108/1010/1013/1016V-GA1, CMB-P1016V-HA1
<WCB>
Connectable unit
CMB-PW202V-J
PURY-(E)P200-350YJM-A(BS)
PQRY-P200-300YHM-A
*1 In case of WCB connection, the capacity range will be "50 to 130%".