- 7 -
(2) PWFY-P100, 200VM-E-AU
300
600
Fig. A
Service space
(front side)
T
op view
400
Piping space
(right side)
P200:Use the Expansion joint
of
accessories
Drain (R1 screw)
ø
9.52 <Brazed>
ø
27 Knockout hole
<Hole for control wiring>
ø
27 Knockout hole
<Hole for power supply>
W
ater outlet
(RC3/4 screw)
W
ater inlet
(R3/4 screw)
P100:
ø
15.88 <Brazed>
P200:
ø
19.05 <Brazed>
ø
27 Knockout hole
<Hole for external wiring input>
ø
27 Knockout hole
<Hole for external wiring output>
Connection pipe of outdoor unit
(Gas)
Connection pipe of outdoor unit
(Liquid)
Front view
Right side view
Control box
Service panel
T
op view
2X2-
ø
14 Hole
525
(Mounting pitch
)
450
(
Mounting pitch)
300
800
205
500
<Accessories>
●Y
-type strainer (RC3/4)
·····························
1pc.
●Heat Insulation material
····························
1pc.
●Connector set
············································
2set
●Expansion joint (P200)
······························
2pcs.
[From RC3/4 to RC1]
Note 1.Ensure no rain water or debris can enter the unit through any gaps around
wiring or piping.
2.Ensure adequate service space is right around the unit, according to Fig
A.
3.Please always make water circulate or add the brine to the circulation water
when the ambient temperature becomes 0
°C
or less.
4.The unit is not designed for outside installations.
5.Install the unit in an environment where the wet bulb
T
emp.
will not exceed 32degC.
6.Please always make water circulate or pull out the circulation
water completely when not using it.
7.The water circuit must use the closed circuit.
8.Please don't use the steel material for the water piping material.
9.Connect the strainer which is put as accessory to water inlet pipe.
91
91
35
55
35
480
102
206
134
11
4
100
191
46
60
140
80
165
54
<Unit:mm>