II
Restrictions ]
- 53 -
HWE0803A
GB
(2) Size of the pipe that fits the main BC controller ports
P72 - P240 models
The ports of the BC controller accommodates the pipes on P24 - P54 models of indoor units. To connect other types of indoor
units, follow the procedure below.
1) To connect P06 - P18 models of indoor units use the reducer that is supplied with the BC controller.
2) To connect the units between the P72 and P96 models of indoor units (or when the total capacity of indoor units is P55
or above), use a junction pipe kit and merge the two nozzles.
3) To connect multiple indoor units to a port (or to a junction pipe)
Maximum total capacity of connected indoor units: P54 or below (in a system with a junction pipe: P96 or below)
Maximum number of connectable indoor units: 3 units
Branch joint: Use CMY-Y102S-G2 (optional accessory).
Refrigerant pipe selection (size of the pipes in sections A and B in the figure above): Select the proper based on the total
capacity of the downstream indoor units, using the table below as a reference.
Unit : mm [inch]
Total capacity of indoor units
Liquid pipe
Gas pipe
P54 or below
ø9.52 [3/8"]
ø15.88 [5/8"]
P55 - P72
ø9.52 [3/8"]
ø19.05 [3/4"]
P73 - P96
ø9.52 [3/8"]
ø22.2 [7/8"]
Unit : mm [inch]
Operation
Pipe sections
High pressure side (Liquid)
Low-pressure side (Gas)
Outdoor unit
side
PURY-P72THMU-A
PURY-P72YHMU-A
ø15.88 [5/8"]
(Brazed connection)
ø19.05 [3/4"]
(Brazed connection)
PURY-P96THMU-A
PURY-P96YHMU-A
ø19.05 [3/4"]
(Brazed connection)
ø22.2 [7/8"]
(Brazed connection)
PURY-P120THMU-A
PURY-P120YHMU-A
ø28.58 [1-1/8"]
(Brazed connection)
PURY-P144TSHMU-A
PURY-P144YSHMU-A
ø22.2 [7/8"]
(Brazed connection)
PURY-P168TSHMU-A
PURY-P168YSHMU-A
PURY-P192TSHMU-A
PURY-P192YSHMU-A
PURY-P216TSHMU-A
PURY-P216YSHMU-A
ø28.58 [1-1/8"]
(Brazed connection)
PURY-P240TSHMU-A
PURY-P240YSHMU-A
Indoor unit side
ø9.52 [3/8"] (Flare connection)
ø15.88 [5/8"] (Flare connection)
A
B
Indoor
Indoor
Indoor
P18 model or below P24 - P54 models P72 or P96 models
*2
Junction pipe kit
(Model name:CMY-R160-J)
(Optional accessory)
BC controller (main)
To outdoor unit
Connection: Brazed connection
*1
Reducer
(Standard supplied parts)
Maximum of 3 units per port
Total capacity of P54 or below
(All units connected to the same port
must be in the same operating mode.)
3*
Indoor
Indoor
Indoor
Branch joint (Model name:CMY-Y102S-G2)
(Optional
accessory)
Содержание PURY-P120Y(T)HMU-A
Страница 1: ......
Страница 11: ... 2 ...
Страница 25: ... 16 ...
Страница 65: ... 56 ...
Страница 88: ... III Outdoor Unit Components 79 HWE0803A GB 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 89: ... 80 ...
Страница 91: ... 82 ...
Страница 99: ... 90 ...
Страница 101: ... 92 ...
Страница 115: ... 106 ...
Страница 116: ... 107 HWE0803A GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 109 2 Principal Parts and Functions 116 ...
Страница 117: ... 108 ...
Страница 133: ... 124 ...
Страница 161: ... 152 ...
Страница 163: ... 154 ...
Страница 187: ... 178 ...
Страница 340: ... 331 HWE0803A GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 333 ...
Страница 341: ... 332 ...
Страница 387: ......