IX
Troubleshooting ]
- 206 -
HWE0803A
GB
1. Error
Code
Heatsink overheat protection
2. Error definition and error detection method
When the heat sink temperature (THHS) remains at or above TOH is detected.
3. Cause, check method and remedy
Refer to section -7- "Inverter (THMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the
inverter.(page 293)
4230
(THMU-A)
Model
TOH
P72 model
100°C [212°F]
P96, P120 models
90°C [194°F]
Cause
Check method and remedy
(1)
Fan board failure
Refer to IX [4] -7- (2) [6].(page 296)
(2)
Outdoor unit fan failure
Check the outdoor unit fan operation.
If any problem is found with the fan operation, check the fan motor. ->Refer to
IX [4] -7- (2) [5].(page 296)
(3)
Air passage blockage
Check that the heat sink cooling air passage is not blocked
(4)
THHS failure
P72 model
1)
Check for proper installation of the INV board IGBT. (Check for proper instal-
lation of the IGBT heatsink.)
2)
Check for proper installation of the INV board IGBT.
->If an abnormal value appears, replace the INV board.
P96 andP120 models
3)
Check the THHS sensor reading on the LED monitor.
->If an abnormal value appears, check the sensor resistance, and replace the
sensor as necessary.
Содержание PURY-P120Y(T)HMU-A
Страница 1: ......
Страница 11: ... 2 ...
Страница 25: ... 16 ...
Страница 65: ... 56 ...
Страница 88: ... III Outdoor Unit Components 79 HWE0803A GB 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 89: ... 80 ...
Страница 91: ... 82 ...
Страница 99: ... 90 ...
Страница 101: ... 92 ...
Страница 115: ... 106 ...
Страница 116: ... 107 HWE0803A GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 109 2 Principal Parts and Functions 116 ...
Страница 117: ... 108 ...
Страница 133: ... 124 ...
Страница 161: ... 152 ...
Страница 163: ... 154 ...
Страница 187: ... 178 ...
Страница 340: ... 331 HWE0803A GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 333 ...
Страница 341: ... 332 ...
Страница 387: ......