VII
Control ]
- 148 -
HWE0803A
GB
(3) BC controller (cooling only, heating only, cooling main and heating main modes)
Start
Breaker
turned on
Operation
command
Error command to
outdoor unit
Error stop
Self-holding of
protection function
Error command to
indoor unit
Error mode
*Note 1
YES
YES
YES
NO
NO
Fan
NO
All units in the
same mode
Solenoid valves OFF
LEV Fully closed
1. Determination of operation mode
(Cooling only, Heating only, Mixture
of units in cooling and heating)
2. Transmitted to the outdoor unit
3
3
Operation
mode
Note 1. The system may go into the error mode on either the indoor unit side or the BC controller or outdoor
unit side. If some of the indoor units are experiencing a problem, only those indoor units that are
experiencing the problem will stop. If the BC controller or the outdoor unit is experiencing a problem,
all the connected units will stop.
Operation
mode
Operation
mode
Cooling Only
Heating Only
Cooling Main
Heating Main
Mixture of units in cooling and heating
Reception of operation mode
command from the outdoor unit
Protection function
self-holding cancelled.
Normal operation
Error
Unit in the stopped state
Содержание PURY-P120Y(T)HMU-A
Страница 1: ......
Страница 11: ... 2 ...
Страница 25: ... 16 ...
Страница 65: ... 56 ...
Страница 88: ... III Outdoor Unit Components 79 HWE0803A GB 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 89: ... 80 ...
Страница 91: ... 82 ...
Страница 99: ... 90 ...
Страница 101: ... 92 ...
Страница 115: ... 106 ...
Страница 116: ... 107 HWE0803A GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 109 2 Principal Parts and Functions 116 ...
Страница 117: ... 108 ...
Страница 133: ... 124 ...
Страница 161: ... 152 ...
Страница 163: ... 154 ...
Страница 187: ... 178 ...
Страница 340: ... 331 HWE0803A GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 333 ...
Страница 341: ... 332 ...
Страница 387: ......