IX
Troubleshooting ]
- 226 -
HWE0803A
GB
1. Error
Code
Open-circuited IPM/Loose ACCT connector (Detail code 119)
2. Error definition and error detection method
Presence of enough current cannot be detected during the self-diagnostic operation immediately before inverter startup.
3. Cause, check method and remedy
P72 model
P96 and P120 models
Refer to section -7- "Inverter (THMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the
inverter.(page 293)
5301
(THMU-A)
Cause
Check method and remedy
(1)
Inverter output wiring problem
Check output wiring connections.
Confirm that the U- and W-phase output cables are put through CT12
and CT22 on the INV board respectively.
(2)
Inverter failure
Refer to IX [4] -7- (2) [3], [4].(page 296)
(3)
Compressor failure
Refer to IX [4] -7- (2) [2].(page 295)
Cause
Check method and remedy
(1)
ACCT sensor disconnection
Check the connection of the connector (CNCT2) on the INV board.
Check for proper mounting of ACCT.
(2)
ACCT sensor failure
Refer to IX [4] -7- (4).
(3)
Inverter failure
Refer to IX [4] -7- (2) [3], [4].(page 296)
(4)
Compressor failure
Refer to IX [4] -7- (2) [2].(page 295)
Содержание PURY-P120Y(T)HMU-A
Страница 1: ......
Страница 11: ... 2 ...
Страница 25: ... 16 ...
Страница 65: ... 56 ...
Страница 88: ... III Outdoor Unit Components 79 HWE0803A GB 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 89: ... 80 ...
Страница 91: ... 82 ...
Страница 99: ... 90 ...
Страница 101: ... 92 ...
Страница 115: ... 106 ...
Страница 116: ... 107 HWE0803A GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 109 2 Principal Parts and Functions 116 ...
Страница 117: ... 108 ...
Страница 133: ... 124 ...
Страница 161: ... 152 ...
Страница 163: ... 154 ...
Страница 187: ... 178 ...
Страница 340: ... 331 HWE0803A GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 333 ...
Страница 341: ... 332 ...
Страница 387: ......