IX
Troubleshooting ]
- 249 -
HWE0803A
GB
1. Error
Code
Capacity code setting error
2. Error definition and error detection method
Connection of incompatible (wrong capacity code) indoor unit or outdoor unit
3. Error source, cause, check method and remedy
7101
Error source
Cause
Check method and remedy
Outdoor unit
Indoor unit
(1)
The model name (capacity code) set by
the switch (SW2) is wrong.
1)
Check the model name (capacity code) of the in-
door unit which has the error source address set by
the switch (SW2 on indoor unit board).
When the model name set by the switch is different
from that of the unit connected, turn off the power
source of the outdoor and the indoor units, and
change the setting of the capacity code.
*The capacity of the indoor unit can be
confirmed by the self-diagnosis function
(SW1 operation) of the outdoor unit.
Outdoor unit
(2)
The model selection switches (SW5-1 -
5-4) on the outdoor unit are set incor-
rectly.
Check the setting for the model selection switch on
the outdoor unit (Dipswitches SW5-1 - 5-4 on the
outdoor unit control board).
72 model
96 model
120 model
SW5
OFF
ON OFF OFF
ON
ON OFF OFF
OFF OFF ON
OFF
1
2
3
4
Model
Содержание PURY-P120Y(T)HMU-A
Страница 1: ......
Страница 11: ... 2 ...
Страница 25: ... 16 ...
Страница 65: ... 56 ...
Страница 88: ... III Outdoor Unit Components 79 HWE0803A GB 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 89: ... 80 ...
Страница 91: ... 82 ...
Страница 99: ... 90 ...
Страница 101: ... 92 ...
Страница 115: ... 106 ...
Страница 116: ... 107 HWE0803A GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 109 2 Principal Parts and Functions 116 ...
Страница 117: ... 108 ...
Страница 133: ... 124 ...
Страница 161: ... 152 ...
Страница 163: ... 154 ...
Страница 187: ... 178 ...
Страница 340: ... 331 HWE0803A GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 333 ...
Страница 341: ... 332 ...
Страница 387: ......