IX
Troubleshooting ]
- 329 -
HWE0803A
GB
5. LEV
6. Solenoid
valve
Work procedure
Explanatory figure
(1) Remove the service panel.(Refer to (1)-1.2.3.)
(2) Replace the LEV in trouble.
Secure enough service space in the ceiling for welding
operation, and conduct the work carefully.If required,
dismount the unit from the ceiling, and conduct the work.
*Special care must be taken when replacing heavy parts.
Work procedure
Explanatory figure
(1) Remove the service panel.(Refer to (1)-1.2.3.)
(2) Remove the connector of the solenoid valve in trou-
ble.
(3) Remove the solenoid valve coil.
1) The coils on the solenoid valves SVA, SVB, SVM1 and
SVM2 can be serviced through the inspection door. SVC
is accessible for replacement by removing the four
mounting screws on the rear panel and removing the
panel (if enough space is available on the back). (SVM1
is present only on the G and GA types, SVM2 on the GA
type.)
LEV3
LEV1
LEV2
SVM2
SVM2b
CMB-1016NU-G
Double-pipe heat exchanger
CMB-1016NU-GA
Solenoid valve
Содержание PURY-P120Y(T)HMU-A
Страница 1: ......
Страница 11: ... 2 ...
Страница 25: ... 16 ...
Страница 65: ... 56 ...
Страница 88: ... III Outdoor Unit Components 79 HWE0803A GB 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 89: ... 80 ...
Страница 91: ... 82 ...
Страница 99: ... 90 ...
Страница 101: ... 92 ...
Страница 115: ... 106 ...
Страница 116: ... 107 HWE0803A GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 109 2 Principal Parts and Functions 116 ...
Страница 117: ... 108 ...
Страница 133: ... 124 ...
Страница 161: ... 152 ...
Страница 163: ... 154 ...
Страница 187: ... 178 ...
Страница 340: ... 331 HWE0803A GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 333 ...
Страница 341: ... 332 ...
Страница 387: ......