Troubleshooting ]
- 291 -
HWE0803A
GB
Check whether the BC board output signal corresponds with the solenoid valve operation correspond.
1) SVA, SVB, SVC
SVA, SVB, and SVC turn on or off according to the indoor unit operation mode.
SVM1 and SVM2
SVM1 and SVM2 turn on or off according to the indoor unit operation mode.
2) SVA, SVB, SVC
Measure the temperature at the upstream and downstream pipes
and
of SVA.
Measure the temperature at the upstream and downstream
pipes and
of SVA.
Mode
Cooling
Heating
Stopped
Defrost
Fan
Port
SVA
ON
OFF
OFF
OFF
OFF
SVB
OFF
ON
OFF
OFF
OFF
SVC
ON
OFF
OFF
OFF
ON
Operation
mode
Cooling only
Cooling main
Heating only
Heating main
Defrost
Stopped
SVM1
ON
Pressure dif-
ferential con-
trol OFF or
ON
OFF
OFF
ON
OFF
SVM2
OFF
OFF
Pressure dif-
ferential con-
trol OFF or
ON
Pressure dif-
ferential con-
trol OFF or
ON
OFF
OFF
Содержание PURY-P120Y(T)HMU-A
Страница 1: ......
Страница 11: ... 2 ...
Страница 25: ... 16 ...
Страница 65: ... 56 ...
Страница 88: ... III Outdoor Unit Components 79 HWE0803A GB 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 89: ... 80 ...
Страница 91: ... 82 ...
Страница 99: ... 90 ...
Страница 101: ... 92 ...
Страница 115: ... 106 ...
Страница 116: ... 107 HWE0803A GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 109 2 Principal Parts and Functions 116 ...
Страница 117: ... 108 ...
Страница 133: ... 124 ...
Страница 161: ... 152 ...
Страница 163: ... 154 ...
Страница 187: ... 178 ...
Страница 340: ... 331 HWE0803A GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 333 ...
Страница 341: ... 332 ...
Страница 387: ......