VIII
Test Run Mode ]
- 171 -
HWE0803A
GB
Operation
Outdoor unit model
PURY-P240TSHMU-A
PURY-P120THMU-A
PURY-P120THMU-A
Model name of BC controller
CMB-P1013NU-GA
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
26.7°C/19.4°C [80°F/67°F]
Outdoor
35°C/- [95°F/-]
Indoor unit
No. of connected units
Unit
7
No. of units in operation
7
Model
-
24/36/36/36/36/36/36
Piping
Main pipe
m
[ft]
5 [16-3/8"]
Branch pipe
10 [32-3/4"]
Total pipe length
75 [229-5/8"]
Fan speed
-
Hi
Amount of refrigerant
kg
[lbs-oz]
44.6 [98]
Outdoor
unit
Electric current
A
60.2
Voltage
V
230
Compressor frequency
Hz
75
75
LEV open-
ing
Indoor unit
Pulse
200/275/275/275/275/275/275
BC controller (1/2/3)
2000/2000/290
Pressure
High pressure(63HS1)/
Low pressure(63LS)
MPa
[psi]
2.82/0.89
[409/129]
2.82/0.89
[409/129]
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
2.73/2.73
[395/395]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C
[°F]
82 [180]
82 [180]
Heat exchanger outlet
(TH3)
43 [109]
43 [109]
Accumulator inlet
8 [46]
8 [46]
Accumulator outlet
8 [46]
8 [46]
Compressor inlet
20 [68]
20 [68]
Compressor shell bottom
42 [108]
42 [108]
Indoor unit
LEV inlet
22 [72]
Heat exchanger inlet
11 [52]
Содержание PURY-P120Y(T)HMU-A
Страница 1: ......
Страница 11: ... 2 ...
Страница 25: ... 16 ...
Страница 65: ... 56 ...
Страница 88: ... III Outdoor Unit Components 79 HWE0803A GB 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 89: ... 80 ...
Страница 91: ... 82 ...
Страница 99: ... 90 ...
Страница 101: ... 92 ...
Страница 115: ... 106 ...
Страница 116: ... 107 HWE0803A GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 109 2 Principal Parts and Functions 116 ...
Страница 117: ... 108 ...
Страница 133: ... 124 ...
Страница 161: ... 152 ...
Страница 163: ... 154 ...
Страница 187: ... 178 ...
Страница 340: ... 331 HWE0803A GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 333 ...
Страница 341: ... 332 ...
Страница 387: ......