Check code
Abnormal points and detection methods
Causes and check points
<63L equipped model>
(1) Low pressure (63L is in operation)
Abnormal if 63L operates (under-0.03MPa) during compressor
operation.
63L : Low pressure switch
LEV : Electronic expansion valve
SV1 : Solenoid valve
TH7 : Thermistor <Ambient>
Defective operation of stop valve (not fully open)
Clogged or broken pipe.
Malfunction or locked outdoor fan motor
Short-cycle of outdoor unit
Dirt of outdoor heat exchanger
Remote controller transmitting error caused by noise interference
Contact failure of outdoor multi controller circuit board connector
Defective outdoor multi controller circuit board
Short-cycle of indoor unit
Decreased airflow, clogged filter, or dirt on indoor unit.
Malfunction or locked indoor fan motor.
Decreased airflow caused by defective inspection
of outdoor temperature thermistor (It detects lower
temperature than actual temperature.)
Indoor LEV performance failure
Malfunction of fan driving circuit
SV1 performance failure
Defective low-pressure sensor
Malfunction of low-pressure sensor input circuit on
outdoor multi controller circuit board
●Diagnosis of defectives
Make sure to turn the power OFF before connecting/disconnecting any connectors, or replacing boards.
Diagnosis
Remedy
1300
Low pressure trouble
Yes
Yes
Yes
No
No
Yes
Yes
No
No
No
Is the outdoor stop valve
(liquid/ gas) fully open?
Does the outdoor fan rotare
while the operation?
Does the indoor fan rotate while
the operation?
Is the indoor unit filter clogged?
Is the indoor unit short-cycled?
Open the stop valve (liquid/ gas) fully.
Check the outdoor fan motor.
Refer to "How to check the parts" on
outdoor unit service manual.
Check the indoor fan motor.
Refer to "How to check the parts" on
indoor unit service manual.
Clean the filter.
Solve the short-cycle.
(short-cycled)
(filter clogged)
(no short-cycle)
(no clog)
Continue to the next page
Chart 1 of 3