![Mitsubishi Electric PUMY-P112VKM1 Скачать руководство пользователя страница 9](http://html.mh-extra.com/html/mitsubishi-electric/pumy-p112vkm1/pumy-p112vkm1_service-manual_1811222009.webp)
9
3
SPECIFICATIONS
Model
PUMY-P112VKM1(-BS)
PUMY-P125VKM1(-BS)
PUMY-P140VKM1(-BS)
Power source
1-phase 220/240
V, 50 Hz
Cooling capacity
(Nominal)
kW*
1
12.5
14.0
15.5
kcal/h*
1
10,750
12,040
13,330
BTU/h*
1
42,650
47,768
52,886
Power input
kW
2.79
3.46
4.52
Current input
A
12.87/ 12.32/ 11.80
15.97/ 15.27/ 14.64
20.86/ 19.95/ 19.12
COP
kW/kW
4.48
4.05
3.43
Temp. range of
cooling
Indoor temp.
W.B.
15 to 24
°C
Outdoor temp.
D.B.
−5 to 46
°C
Heating capacity
(Nominal)
kW*
2
14.0
16.0
18.0
kcal/h*
2
12,040
13,760
15,480
BTU/h*
2
47,768
54,592
61,416
Power input
kW
3.04
3.74
4.47
Current input
A
14.03/ 13.42/ 12.86
17.26/ 16.51/ 15.82
20.63/ 19.73/ 18.91
COP
kW/kW
4.61
4.28
4.03
Temp. range of
heating
Indoor temp.
D.B.
15 to 27
°C
Outdoor temp.
W.B.
−20 to 15
°C
Indoor unit
connectable
Total capacity
50 to 130% of outdoor unit capacity
Model / Quantity Citymulti
15 - 125/ 9
15 - 140/ 10
15 - 140/ 12
Branch box
15 - 100/ 8
15 - 100/ 8
15 - 100/ 8
Mixed system
15 - 125(*
3
)/ 10
15 - 140/ 10*
4
15 - 125/ 10*
4
Sound pressure level
(measured in anechoic room)
dB <A>
49/ 51
50/ 52
51/ 53
Power pressure level
(measured in anechoic room)
dB <A>
-
-
-
Refrigerant
piping diameter
Liquid pipe
mm (in)
9.52 (3/8)
Gas pipe
mm (in)
15.88 (5/8)
FAN *2
Type x Quantity
Propeller Fan x 2
Air flow rate
m3/min
110
L/s
1,833
cfm
3,884
Control, Driving mechanism
DC control
Motor output
kW
0.06+0.06
External static press.
0
Compressor
Type x Quantity
Scroll hermetic compressor x 1
Manufacture
Mitsubishi Electric Corporation
Starting method
Inverter
Capacity control
%
Cooling 26 to 100
Heating 20 to 100
Cooling 24 to 00
Heating 18 to 100
Cooling 21 to 100
Heating 17 to 100
Motor output
kW
2.9
3.5
3.9
Case heater
kW
0
Lubricant
FV50S(2.3litter)
External finish
Galvanized Steel Sheet
Munsell No. 3Y 7.8/1.1
External dimension HxWxD
mm
1,338 x 1,050 x 330(+25)
in
52-11/16 x 41-11/ 32 x 13 (+1)
Protection
devices
High pressure protection
High pressure Switch
Inverter circuit (COMP./FAN)
Overcurrent detection, Overheat detection(Heat sink thermistor)
Compressor
Compressor thermistor, Over current detection
Fan motor
Overheating, Voltage protection
Refrigerant
Type x original charge
R410A 4.8kg
Control
Electronic Expansion Valve
Net weight
kg (lb)
123 (271)
Heat exchanger
Cross Fin and Copper tube
HIC circuit (HIC: Heat Inter-Changer)
HIC circuit
Defrosting method
Reversed refrigerant circuit
Drawing
External
BK01N346
Wiring
BH78B813
Standard
attachment
Document
Installation Manual
Accessory
Grounded lead wire x2
Optional parts
Joint: CMY-Y62-G-E
Header: CMY-Y64/68-G-E
Branch box: PAC-MK30/50BC
Remarks
Unit converter
kcal/h = kW × 860
BTU/h = kW × 3,412
cfm = m3/min x 35.31
lb = kg/0.4536
Above specification data is
subject to rounding
variation.
*
1
Nominal cooling conditions
*
2
Nominal heating conditions
Indoor :
27
°C
D.B./19
°C
W.B. [81
°
F D.B/66
°
F W.B.]
20
°C
D.B. [68
°
F D.B.]
Outdoor :
35
°C
D.B. [95
°
F D.B.]
7
°C
DB/6
°C
W.B. [45
°
F D.B./43
°
F W.B.]
Pipe length :
7.5 m [24-9/16 ft]
7.5 m [24-9/16 ft]
Level difference :
0 m [0 ft]
0 m [0 ft]
Note : 1. Nominal conditions *
1
, *
2
are subject to ISO 15042.
2. Due to continuing improvement, above specifications may be subject to change without notice.
*
3
Up to P100 when connecting via branch box.
*
4
Up to 11 units when connecting via 2 branch boxes.
OCH576
Содержание PUMY-P112VKM1
Страница 155: ...155 OCH576 ...