112
The black square (
■
) indicates a switch position.
PUMY-P112/125/140YKM1(-BS)
Continue to the next page
8-5. INTERNAL SWITCH FUNCTION TABLE
PUMY-P112/125/140VKM1(-BS)
Switch
Step
Function
Operation in Each Switch Setting
Remarks
Purpose
Additional Information
ON
OFF
When to Set
SWU1
unit digit
SWU2
tens digit
Rotary switch
Before turning
the power ON
<Initial settings>
SW1 Digital
Display
Switch
1–8
Can be set either during operation or not.
<Initial settings>
T
o
display
outdoor
unit's
information
to
the LED on outdoor multi controller circuit board. Refer to "8-10. OUTDOOR UNIT
INFORMA
TION DISPLA
Y".
SW2
Function
Switch
1
Selects operating system startup
With centralized controller
Without centralized controller
Before turning
the power ON
<Initial settings>
Turn ON when the centralized controller is connected to the outdoor unit.
•
SW2-1 must be turned ON if a central controller is connected to the syst
em.
An example of this would
be
a TC-24,
EB50A, AG150, AE50
or AE200.
If SW2-1 is not turned on, while using a central controller
, in rare circumstances problems may be
encountered such as indoor units not responding to group commands.
Therefore, turning SW2-1 ON
is recommended if a central controller is used.
•
Group setting of 2 or more
A-IC units which
is connected to branch box via centrilized controller is not allowed.
2
Connection Information Clear Switch
Clear
Do not clear
When relocating units or connecting additional units.
—
3
Abnormal data clear switch input
Clear abnormal data
Normal
OFF to ON any time after the power is turned on.
T
o delete an error history
.
4
Pump down
Run
adjustment
mode
Normal
During compressor
running
To facilitate outdoor unit the pumping down operation. Frequency = Fixed to 65 Hz
Indoor-electronic expansion valve = Fully open
Outdoor fan step = Fixed to 10
Please refer to a section referring to the pumping down on outdoor units Installation Manuals.It might not be possible to collect all the refrigerant if the amount is excessive.
5
—
—
—
—
—
—
6
—
—
—
—
—
—
SW3 T
rial
operation
1
ON/OFF from outdoor unit*
1
ON
OFF
Any time after the power is turned ON.
<Initial settings>
—
—
2
Mode setting
Heating
Cooling
—
—
SW4/
SW8
Model
Switch
1–6
MODEL
SELECTION 1:ON 0:OFF
Before the power
is turned ON.
<Initial settings>
Set for each capacity
.
—
—
SW5
Function
switch
1
Demand control setting for
Australia
Aus
trali
a s
etting
Normal*
2
Can be set when
of
f or during
operation
<Initial settings>
Turn ON to activate the demand control for Australia.
(Do not turn this ON if the unit is in outside
Australia)
2
Change
the
indoor
unit's
LEV
opening at start-up
Enable
Normal
To set the LEV opening at start-up higher than usua
l.
(+150 pulses) To improve the operation with the LEV almost clogged.
The refrigerant flow noise at start-up
become louder
.
3
—
—
—
—
—
4
Auxiliary heater
—
—
OFF to ON during
compressor running.
Tu
rn
ON
w
hen
an
au
xilia
ry
he
ate
r is
co
nn
ect
ed
.
(It transmits a connection permission signal of the auxiliary heater to the connected indoor unit.)
Turn ON only when the auxiliary heater is connected and operated.
5
Change
the
indoor
unit's
LEV
opening at defrost
Enable
Normal
Can be set when
OFF or during
operation
To set the LEV opening higher than usual during defrosting operation. (Only Qj
[
10 is valid, + 300 pulses)
To avoid the discharge temperature increase
and provide efficient defrosting operation.
The refrigerant flow noise during the
defrosting operation become louder
.
6
Switching the target sub cool
(Heating mode)
Enable
Normal
To decrease the target sub cool value.
To reduce the discharge temperature decrease due to refrigerant liquid accumulation in the units.
A refrigerant flow noise might be
generated if the sub cool value is too small.
*
1
T
est run on PWFY
series cannot be run by the outdoor unit. Use a switch on the indoor unit or a remote controller to perform test run.
*
2
Refer to "8-6. OUTDOOR UNIT
INPUT/OUTPUT
CONNECT
OR".
SWU2
(tens digit)
0
1 2
3 4
5
67
89
SWU1
(unit digit)
0
1 2
3 4
5
67
89
1
ON OFF
2
3
4
5
6
7
8
SW4
MODEL
PUMY
-P1
12VKM1
SW8
PUMY
-P125VKM1
PUMY
-P140VKM1
1
ON OFF
2
3
4
5
6
1
ON OFF
2
3
4
5
6
1
ON OFF
2
3
4
5
6
1
ON OFF
2
1
ON OFF
2
1
ON OFF
2
SW4
MODEL
PUMY
-P1
12YKM1
SW8
PUMY
-P125YKM1
PUMY
-P140YKM1
1
ON OFF
2
3
4
5
6
1
ON OFF
2
3
4
5
6
ON OFF
1
ON OFF
2
1
ON OFF
2
1
ON OFF
2
1
2
3
4
5
6
SWU2
(tens digit)
0
1 2
3 4
5
67
89
SWU1
(unit digit)
0
1 2
3 4
5
67
89
1
ON OFF
2
3
4
5
6
7
8
1
ON OFF
2
3
4
5
6
1
ON OFF
2
1
ON OFF
2
3
4
5
6
7
8
OCH576