113
The black square (
■
) indicates a switch position.
1
ON OFF
2
3
4
5
6
7
8
1
ON OFF
2
3
4
5
6
1
ON OFF
2
<Initial settings>
Switch
Step
Function
Operation in Each Switch Setting
Remarks
Purpose
Additional Information
ON
OFF
When to Set
SW5
function
switch
7
During the outdoor unit is in HEA
T
operation, slightly opens the electronic expansion valve on the indoor unit which is in F
AN, ST
OP
, COOL
or thermo-OFF*
4
.
Active
Inactive
Can be set when OFF or during operation
To open the LEV opening higher for units other than in
HE
AT
operation.
To avoid a r
efr
iger
ant shor
tage (
less
capacity)
due to refriger
ant liquid accumulation in the
units which is not in operation.
A
refrigerant
flow
noise
might
be
gene
rated
in units other than the one in operation.
8
During the outdoor unit is in operation, fully opens the electronic expansion valve on the indoor unit which is in FAN, COOL, ST
OP
, or thermo-OFF
.*
5
Enable
Normal
Before turning the
power ON.
To reduce the room temperature increase by setting the LEV opening lower for the units in thermo-OFF
operation.
The refrigerant is more likely to collect in the units with thermo-OFF operation, and causing the units refrigerant shortage. (Results in less capacity and increase of discharge temperature.)
SW6
function
switch
1
—
—
—
—
<Initial settings>
—
—
2
—
—
—
—
—
—
3
—
—
—
—
—
—
4
Change of defrosting control
Enable (For high humidity)
Normal
Can be set
when OFF
or during
operation
To shorten the defrosting prohibition time in high humidity (or heavy snow) region, in order to reduce malfunctions caused by frost .
The performance of the HEA
T operation is somewhat
reduced since the defrosting operation is frequently performed.
5
Ignore
refrigerant
filling
abnormality
Enable
Normal
To ignore the error detection of excessive charge of refrigerant.
The unit can be excessively charged w
ith
refrigerant depending on the operating condition.
Make sure that the unit is not excessively charged with refrigerant before starting operation when servicing or installing the units.
6
Switching the target discharge
pressure (Pdm)
Enable
Normal
To raise the performance by setting the PDm higher during HEA
T operation.
Power consumption is raised due to a higher frequency
. (The performance would not be raise at the
maximum operating frequency
.)
7
Switching (1) the target evaporation temperature (ETm)
Enable
Normal
To raise/reduce the performance by changing the target ETm during COOL
operation.
Switch to raise the performance: raises the performance Switch to reduce the performance: prevents dew condensation
Switching it to raise the performance, it raises the power
consumption, and produces more dew condensation. Switching it to reduce the performance, it makes the
performance insufficient.
8
Switching (2) the target evaporation temperature (ETm)
Enable
Normal
SW7
function
switch
1
Ignore current sensor
abnormality
Enable
Normal
After turning
the power ON.
<Initial settings>
To perform a test run for electrical parts alone without running the compressor
.
Make sure to connect the connector
s to the compr
essor
after checking the electrical parts.Be careful not to get electrical shock while working on electrical parts.
2
Setting to energize the freeze
stat heater (optional part)
During heating operation only
*
6
Include when the heating operation is OFF
.
*
7
Can be set when OFF or during operation
It
re
du
ces sn
ow
o
n
the
ba
se
, even
it
blo
ws in
sid
e
the
unit, by setting the base heater ON while the HEA
T
operation is stopped.
Power consumption raises while the operation is stopped.
3
—
—
—
—
—
—
4
Maximum frequency down at 1
hour after COOL
operation
Enable
Normal
Can be set when OFF or during operation
To reduce dew condensation on the indoor unit by lowering the frequency
.
The performance might be insufficient.
5
—
—
—
—
—
6
Forced defrost
Forced defrost
Normal
During compressor running in HEA
T
mode.
Turn ON when it is necessary to perform the defrosting operation forcedly
.
(
Ef
fective only at start-up, or 10
minutes after the last defrosting operation)
It performs the defrosting operation forcedly
.
(HEA
T operation is stopped temporarily
.)
SW9
Function
Switch
1
Auto change over from remote
controller
(IC with the minimum address)
Enable*
3
Disable
Before turning the
power ON
<Initial settings>
Enables the indoor unit with the minimum address
to select
AUT
O mode, and switches the operation
mode of the other indoor units to the same mode.
Cannot be set when the centralized control
is ON.
2
Switching the Silent/ Demand
mode
Demand control
Silent mode
Can be set when OFF or during operation
—
About the Silent mode/Demand control setting, refer to "8-
6. OU
TD
OOR
U
NIT
IN
PU
T/OU
TP
UT
C
ON
NE
CT
OR
".
*
3
When a PWFY
series is connected, this function is always disable regardless of the switch.
*
4
SW5-7 Opens the indoor-
electronic
expancion valve as a countermeasure against the indoor unit in F
AN, COOL, ST
OP
, or thermo-OFF operation with refrigerant-shortage status due to an accumulation of liquid refrigerant in the indoor unit.
*
5
SW5-8 Countermeasure against room temperature rise for indoor unit in F
AN, COOL, and thermo-OFF (heating) mode.
*
6
During heating operation and the ambient temperature is 4
:
(39°F) or below
, the freeze prevention heater is energized.
*
7
During heating mode is OFF (include thermo-OFF in cooling mode), and the ambient temperature is 4
:
(39°F) or below
, the freeze prevention heater is energized.
1
ON OFF
2
3
4
5
6
SW6-6
OFF
ON
Target Pdm (kg/cm²)
29.5
31.5
SW6-7
OFF
ON
OFF
ON
SW6-8
OFF
OFF
ON
ON
T
arget ETm (
:
)
9
11
6
14
OCH576