![Mitsubishi Electric PUMY-P112VKM1 Скачать руководство пользователя страница 75](http://html.mh-extra.com/html/mitsubishi-electric/pumy-p112vkm1/pumy-p112vkm1_service-manual_1811222075.webp)
Check code
Abnormal points and detection methods
Causes and check points
Abnormal if any of following symptoms are detected;
1
P112/125/140V model
●Decrease of DC bus voltage to 200 V
●Increase of DC bus voltage to 400 V
●DC bus voltage stays at 310V or lower for censecutive 10 seconds
2
P112/125/140Y model
●Decrease of DC bus voltage to 350 V
●Increase of DC bus voltage to 760 V
●Decrease of primary current to 0.1 A
Note:
The detection is active only when the operational frequency is 40 Hz or
more, or the compressor current is 6 A or more.
Decrease/increase of power supply voltage, or T
open-phase
Disconnection of compressor wiring
Malfunction of 52C
Disconnection or contact failure of CN52C
Defective outdoor power circuit board
Malfunction of 52C driving circuit on outdoor multi
controller circuit board
Disconnection of CN5
Disconnection of CN2
Malfunction of primary current detecting circuit on
outdoor power circuit board
●Diagnosis of defectives
Make sure to turn the power OFF before connecting/disconnecting
any connectors, or replacing boards.
Diagnosis
Remedy
4220
Undervoltage/Overvoltage/PAM error/L1 open-phase/
Power synchronization signal error
The black square (■) indicates a switch position.
Chart 1 of 2
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
6
1
7,8
Is there any abnormality on wirings?
Which sub code is displayed?
Does a DC bus voltage raise to
approx. 350 V at PAM driving?
Is there any abnormality on
PAM wirings?
Is there any abnormality at the
PAM circuit on the outdoor power
circuit board?
Is there any abnormality at
the PAM power supply circuit on the
outdoor multi controller circuit board?
a. T open-phase
b. Disconnection of compressor wiring
c. Disconnection of CN52C
d. Disconnection of CN5
e. Disconnection of CN2
The sub codes are displayed
by an operation of SW1 on
the outdoor multi controller
circuit board.
The sub codes are displayed by an
operation of SW1 on the outdoor
multi controller circuit board.
Check the power supply facility.
Correct the wiring.
Replace the outdoor power circuit board
(Defective outdoor power circuit board).
Replace the outdoor multi controller circuit
board. Breakage of wiring for PAM controlling
power supply, and such.
PAM error
ON
OFF
1 2 3 4 5 6 7 8
SW1 Setting
Display on LED1,2
1
2 3 4 5 6 7 8
3: PAM error
6: Input sensor trouble
7: Shortage voltage trouble
8: Overvoltage trouble
3: PAM error
6: Input sensor trouble
7: Undervoltage trouble
8: Overvoltage trouble
Continue to the next page
75
OCH576
Содержание PUMY-P112VKM1