Check code
1500
Superheat due to low discharge temperature trouble
Abnormal points and detection methods
Causes and check points
Abnormal if the discharge superheat is continuously detected less than
or equal to −15 [5°F]* for 5 minutes even though the indoor LEV has
minimum open pulse after the compressor starts operating for 10 minutes.
LEV : Electronic expansion valve
TH4 : Thermistor <Compressor>
63HS : High-pressure sensor
*At this temperature, conditions for the abnormality detection will not be
satisfied if no abnormality is detected on either TH4 or 63HS.
Disconnection or loose connection of TH4
Defective holder of TH4
Disconnection of LEV coil
Disconnection of LEV connector
LEV performance failure
●Diagnosis of defectives
Make sure to turn the power OFF before connecting/disconnecting any connectors, or replacing boards.
Diagnosis
Remedy
Chart 1 of 2
No
Yes
No
Yes
No
Yes
Is the TH4 wiring disconnected?
Is the resistance normal?
Is there any abnormality
such as a half-disconnection or
breakage?
Connect the wiring properly.
Replace the TH4.
Connect the connector properly,
or replace the LEV.
Check the resistance of TH4
Check the connector contact and wiring of
the indoor LEV.
Disconnect the indoor LEV wiring to check
the resistance.
(disconnected)
(connected properly)
0 ···700 k
"
10 ···410 k
"
20 ···250 k
"
30 ···160 k
"
40 ···104 k
"
Continue to the next page
57
OCH576
Содержание PUMY-P112VKM1
Страница 155: ...155 OCH576 ...