32
B. Example of a group operation system with 2 or more outdoor units and a M-NET remote controller.
(Address settings are necessary.)
Examples of
T
ransmission
Cable
Wiring
Wiring Method
Address Settings
a. Always use shielded wire when making connections between the outdoor unit (OC) and the M-NET control indoor unit
(M-IC), as well for all OC-OC, and IC-IC wiring intervals.
b. Use feed wiring to connect terminals M1 and M2 and the ground terminal on the transmission cable terminal block
(TB3) of each outdoor unit (OC) to terminals M1 and M2 on the terminal S on the transmission cable trminal block of
the M-NET control indoor unit (M-IC).
c. Connect terminals M1 and M2 on the transmission cable terminal block of the M-NET control indoor unit (M-IC) that
has the most recent address within the same group to the terminal block on the M-NET remote controller (M-NET RC).
d. Connect together terminals M1, M2 and terminal S on the terminal block for centralized control (TB7) for the outdoor
unit (OC).
e. DO NOT change the jumper connector CN41 on outdoor multi controller circuit board.
f. The earth processing of S terminal for the centralized control terminal block (TB7) is unnecessary. Connect the termi-
nal S on the power supply unit with the earth.
g. Set the address setting switch as follows.
h. The group setting operations among the multiple M-NET control indoor units is done by the M-NET remote controller
(M-NET RC) after the electrical power has been turned on.
Unit
Range
Setting Method
M-IC (Main)
01 to 50
Use the smallest address within the same group of M-NET control indoor units.
M-IC (Sub)
01 to 50
Use an address, other than the M-IC (Main) in the same group of M-NET control
indoor units. This must be in sequence with the M-IC (Main).
Outdoor Unit
51 to 100
Use the smallest address of all the M-NET control indoor units plus 50.
The address automatically becomes “100” if it is set as “01–50”.
Main M-NET Remote Controller
101 to 150
Set at an M-IC (Main) address within the same group plus 100.
Sub M-NET Remote Controller
151 to 200
Set at an M-IC (Main) address within the same group plu
++
s 150.
MA Remote Controller
—
Address setting is not necessary. (Main/ sub setting is necessary.)
A
B
C
E
D
TB7
TB3
M-IC
(51)
TB5
M-NET RC
(01)
M-IC
TB5
(03)
M-IC
TB5
(02)
M-IC
TB5
(04)
M-IC
TB5
(05)
TB5
(07)
IC
TB5
(06)
L
2
L
1
(101)
(105)
(104)
(155)
OC
TB7
(53)
OC
3
Power Supply
Unit
System
controller
L
3
L
6
L
7
L
4
L
5
2
4
1
A
: Group
B
: Group
C
: Group
D
: Shielded Wire
E
: Sub M-NET Remote Controller
( ): Address example
r
r
r
r
M1 M2 S M1 M2 S
M1 M2 S
M1 M2 S
A B
A B
A B
M1 M2 S
M1 M2 S
M1 M2 S
S
M1 M2 S
TB3
M1 M2 S
M1 M2 S
A B
M1 M2
M1 M2 S
M1 M2 S
NO
M-IC
M-NET RC
M-NET RC M-NET RC
OCH576
Содержание PUMY-P112VKM1
Страница 155: ...155 OCH576 ...