12
Operation
PUMY-P112VKM/YKM1(-BS) PUMY-P125VKM/YKM1(-BS) PUMY-P140VKM/YKM1(-BS)
Operating
conditions
Ambient
temperature
Indoor
DB/
WB
27°C/ 19°C
20°C/ —
27°C/ 19°C
20°C/ —
27°C/ 19°C
20°C/ —
Outdoor
35°C
7°C/ 6°C
35°C
7°C/ 6°C
35°C
7°C/ 6°C
Indoor unit
No. of connected units
Unit
2
2
2
No. of units in operation
2
2
2
Model
—
50 x 1/ 63 x 1
63 × 2
63 x 1 / 80×1
Piping
Main pipe
m
5
5
5
Branch pipe
2.5
2.5
2.5
Total pipe length
10
10
10
Fan speed
—
Hi
Hi
Hi
Amount of refrigerant
kg
7.2
7.2
7.2
Outdoor unit
Electric current
A
16.17/ 5.26
17.38/ 5.67
21.67/ 7.12
21.91/ 7.22
25.84/ 8.58
25.54/ 8.48
Voltage
V
230/ 400
230/ 400
230/ 400
Compressor frequency
Hz
67
69
84
86
96
96
LEV
opening
Indoor unit
Pulse
357
421
447
525
511
586
Pressure
High pressure/Low pressure
MPa
2.70/ 0.94
2.86/ 0.70
2.86/ 0.88
2.87/ 0.67
2.95/ 0.85
2.95/ 0.65
Temp. of
each section
Outdoor
unit
Discharge
°C
67.0
71.9
69.7
72.1
70.7
73.2
Heat exchanger outlet
40.2
2.0
40.8
1.3
43.7
0.9
Accumulator inlet
8.7
1.0
8.0
0.2
5.6
−0.6
Compressor inlet
10.7
1.3
9.1
0.1
7.8
−0.7
Indoor unit LEV inlet
18.9
32.4
17.7
33.0
17.0
33.4
Heat exchanger inlet
12.3
55.5
11.1
55.7
10.4
56.8
4-2. STANDARD OPERATION DATA (REFERENCE DATA)
OCH576
Содержание PUMY-P112VKM1