Thermistor
<Suction pipe> (TH6)
Thermistor
<Compressor> (TH4)
Ball valve
and stop
valve fixing
screws
Thermistor
<HIC pipe>
(TH2)
145
OPERATING PROCEDURE
PHOTOS & ILLUSTRATION
Photo 5
(6) Remove 2 electrical parts box fixing screws (4 × 10) and
detach the electrical parts box by pulling it upward. The
electrical parts box is fixed with 2 hooks on the left and 1
hook on the right.
Electrical parts box
Electrical parts
box fixing screws
From the previous page.
Photo 6
Photo 7
Electrical
parts box
5. Removing the thermistor <Ambient> (TH7)
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(3) Disconnect the connector TH7 (red) on the outdoor multi
controller circuit board in the electrical parts box.
(4) Loosen the wire clamps on top of the electrical parts box.
(See Photo 6)
(5) Pull out the thermistor <Ambient> (TH7) from the sensor
holder.
Note: When replacing thermistor <Ambient> (TH7), replace
it together with thermistor <Suction pipe> (TH6), since
they are combined together.
Refer to procedure No.4 above to remove thermistor
<Suction pipe> (TH6).
Photo 8
Lead wire of thermistor <Ambient> (TH7)
Sensor holder
Clamps
High pressure
sensor (63HS)
4. Removing the thermistor <Suction pipe> (TH6)
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(3) Disconnect the connectors, TH6 and TH7 (red), on the
outdoor multi controller circuit board in the electrical parts
box.
(4) Loosen the wire clamps on the side of the electrical parts
box, and next to it.
(5) Pull out the thermistor <Suction pipe> (TH6) from the sen-
sor holder.
Note: When replacing thermistor <Suction pipe> (TH6),
replace it together with thermistor <Ambient> (TH7)
since they are combined together.
Refer to procedure No.5 below to remove thermistor
<Ambient> (TH7).
OCH576
Содержание PUMY-P112VKM1
Страница 155: ...155 OCH576 ...