8
2-4. UNIT SPECIFICATIONS
(2) Method for identifying MULTI-S model
(1) Outdoor Unit
Indoor unit < When using Model 80 >
Outdoor unit <When using model 125 >
P L F Y - P 80 V BM - E
PU M Y - P 125 Y
K M 1 - BS
PAC type
BM
CM
KM
M
KM
LMD
Frequency
conversion
controller
Refrigerant
R407C/R22
R410A
commonness
Refrigerant
R410A
NEW frequency converter
one-to-many air conditioners
(flexible design type)
Indicates equivalent
to Cooling capacity
Indicates equivalent
to Cooling capacity
Power supply
V: Single phase
220/230/240 V, 50 Hz
Power supply
V
: Single phase
220/230/240 V, 50 Hz
Y
: 3-phase
380/400/415 V, 50 Hz
L : Ceiling cassette
K : Wall-mounted type
E : Hidden skylight type
C : Ceiling suspended type
M : Ceiling cassette type
F : Floor standing type
W: Air to Water Unit
M-NET
control
Outdoor unit
model type
Sub-number
M-NET
control
Frequency
conversion
controller
Outdoor unit
MULTI-S
(k cal/ h)
(k cal / h)
Salt proof
type
sub
number
Service Ref.
Capacity Cooling (kW)
Heating (kW)
12.5
14.0
2.9
14.0
16.0
3.5
15.5
18.0
3.9
Compressor (kW)
PUMY-P112VKM1(-BS)
PUMY-P112YKM1(-BS)
PUMY-P125VKM1(-BS)
PUMY-P125YKM1(-BS)
PUMY-P140VKM1(-BS)
PUMY-P140YKM1(-BS)
Cooling/Heating capacity indicates the maximum value at operation under the following condition.
*Cooling
Indoor : D.B. 27 °C/ W.B. 19.0 °C
Outdoor : D.B. 35 °C
Heating
Indoor : D.B. 20 °C
Outdoor : D.B. 7 °C/ W.B. 6 °C
(3) Operating temperature range
Notes:
D.B. : Dry Bulb Temperature
W.B. : Wet Bulb Temperature
*
1
10 to 46°C D.B. : When connecting PKFY-P15/P20/P25VBM, PFFY-P20/25/32VKM and PFFY-P20/25/32 VLE(R)M type indoor unit.
Cooling
W.B. 15 to 24°C
D.B.
−
5 to 46°C*
1
Heating
D.B. 15 to 27°C
W.B.
−
20 to 15°C
Indoor-side intake air temperature
Outdoor-side intake air temperature
■
When connecting fresh air type indoor unit
air type indoor
Capacity of Fresh
Cooling
Heating
Indoor-side and Outdoor-side
P80
D.B. 21 to 43
:
*
2
W.B. 15.5 to 35
:
D.B.
−
10 to 20
:
*
3
intake air temperature
P140
D.B. 21 to 43
:
*
2
W.B. 15.5 to 35
:
D.B.
−
5 to 20
:
*
3
*
2
Thermo-OFF (FAN-mode) automatically starts if the outdoor temp. is lower than 21
:
D.B..
*
3
Thermo-OFF (FAN-mode) automatically starts if the outdoor temp. is higher than 20
:
D.B..
■
When connecting Air to Water Unit
Cooling
Heating
Indoor-side intake water temperature
Outdoor-side intake air temperature
• PWFY series can operate in Heating mode but not in Cooling mode. An indoor unit other than that of PWFY series can
operate in Cooling mode.
• A PWFY series and other series cannot operate simultaneously.
• The operation of PWFY series takes precedence over other series. While a PWFY series is operating, other series do not operate.
• The set temperature on the remote controller represents the target temperature of the outlet water.
*
4
*
4
D.B. 10 to 45
:
*
4
W.B.
−
20 to 15
:
OCH576
Содержание PUMY-P112VKM1
Страница 155: ...155 OCH576 ...