Check code
Abnormal points and detection methods
Causes and check points
(1) Abnormal if TH4 falls into following temperature conditions;
●exceeds 110 [230°F] continuously for 5 minutes
●exceeds 125 [257°F]
(2) Abnormal if a pressure detected by the high-pressure sensor and
converted to saturation temperature exceeds 40
[104°F]during
defrosting, and TH4 exceeds 110
[230°F].
TH4: Thermistor <Compressor>
LEV: Electronic expansion valve
Malfunction of stop valve
Over-heated compressor operation caused by
shortage of refrigerant
Defective thermistor
Defective outdoor multi controller circuit board
LEV performance failure
Defective indoor controller board
Clogged refrigerant system caused by foreign
object
Refrigerant shortage while in heating operation
(Refrigerant liquid accumulation in compressor while
indoor unit is OFF/thermo-OFF.)
●Diagnosis of defectives
Make sure to turn the power OFF before connecting/disconnecting any connectors, or replacing boards.
Diagnosis
Remedy
1102
Compressor temperature trouble
Yes
Yes
No
Yes
Yes
No
No
No
Is 5101 displayed when restarted?
Is the outdoor stop valve (liquid/
gas) fully open?
Is there a refrigerant leak?
Is there any abnormality on
connectors/wires such as a disconnection,
half-disconnection or breakage?
Check the connection for thermistor wiring
and indoor controller board connector.
Refer to the diagnosis of check code 5101.
Open the stop valve (liquid/ gas) fully.
Repair the refrigerant leakage.
Connect the connector properly
(Repair or replace it in case of a breakage).
(5101)
(1102)
(no leak)
Continue to the next page
Chart 1 of 2
48
49
OCH576