58
7 FUNCTIONS
7.1 Hardware Logic Control Function
7
FUNCTIONS
This chapter describes the details on the functions that can be used in the flexible high-speed I/O control module and their
setting methods.
7.1
Hardware Logic Control Function
Users can create the hardware logic to perform a desired control with the configuration tool.
For details, refer to the following.
Page 103 CREATING A HARDWARE LOGIC
7.2
Error History Function
The errors that occurred in the flexible high-speed I/O control module are stored in the buffer memory areas (Un\G8010 to
Un\G8169) as error history.
Up to 16 errors can be stored.
Processing of the error history function
The error code and error time of each error are stored in Error history No. 1 (start address: Un\G8010) and sequentially
thereafter. The error time is stored as shown below.
Ex.
The following shows the case of Error history No. 1.
*1 Value of when an error occurred at 10:35:40 on Friday, April 24th, 2015
Clearing the error history
The error history can be cleared with one of the following methods.
• Turning off the power
• Resetting the CPU module
• Setting Clear setting of error history (Un\G8002) to Clear the history (1) and turning on and off Error clear request (YF)
Item
Description
Storage example
First two digits of the year/last two
digits of the year
Stored as a BCD code.
2015H
Month/day
0424H
Hour/minute
1035H
Second
40H
Day of the week
For each day of the week, one of the following values is stored as a BCD code.
Sunday: 0H, Monday: 1H, Tuesday: 2H, Wednesday: 3H, Thursday: 4H, Friday: 5H,
Saturday: 6H
5H
b15
b8
b7
b0
to
to
Error code
First two digits of the year
Last two digits of the year
Month
Day
Hour
Minute
Second
Day of the week
System area
to
Un\G8010
Un\G8014
Un\G8013
Un\G8012
Un\G8011
Un\G8015
Un\G8019