124
9 CREATING A HARDWARE LOGIC
9.1 Main Blocks in the Hardware Logic Outline Window
Parameter
The following table shows the parameters of the external output block.
• Parameters of "User Address Setting"
*1 The available buffer memory addresses are common in OUT 0 to OUT 7 and OUT 0_DIF to OUT 5_DIF. Each external output block is
assigned to the bits of the specified buffer memory as follows.
*2 The external output block where Forced output enabled (1) is set outputs a signal according to the setting value (forced output value) of
the buffer memory area specified with "Forced Output". The input from "Input" terminal is not reflected to the external output.
Variable name
Data type
Valid range
Default value
Description
Logic Select
Bit
Non-Inversion
Inversion
Non-Inversion
Set Non-Inversion or Inversion for input signals.
Delay Time (Step)
Word
0 to 64
0
Adjust the signal output timing. A delay time can be set
with the combination of "Delay Time (Step)" and "Delay
Time (Unit)". Setting the number of steps to 0 disables
the delay.
Delay Time (Unit)
Word
12.5ns
25ns
50ns
0.1
μ
s
1
μ
s
10
μ
s
100
μ
s
1ms
12.5ns
Adjust the signal output timing. A delay time can be set
with the combination of "Delay Time (Unit)" and "Delay
Time (Step)".
Error-time Output Mode
Word
OFF
ON
HOLD
OFF
Set output signals at occurrence of an error in the CPU
module to OFF fixed, ON fixed, or holding output
status. This setting is also applied to output signals at a
hardware logic control stop.
User Address Setting
Set the buffer memory addresses used in the external
output block. Click the [Detail] button to open the "User
Address Setting" window.
Variable name
Data type
Valid range
Description
Enable Forced Output
Word
1000 to 1099
Specify the buffer memory address to enable or disable
the forced output.
Whether the forced output is enabled or disabled can
be set by setting the following values for the specified
buffer memory.
0: Forced output disabled
1: Forced output enabled
Forced Output
Word
1000 to 1099
Specify the buffer memory address to set the status of
the forced output signal.
Whether the signal status is set to off or on can be set
by setting the following values for the specified buffer
memory.
0: OFF output
1: ON output
External terminal monitor
Word
1000 to 1099
Specify the buffer memory address to store the
external terminal status.
0: OFF output
1: ON output
bit15
bit14
bit13
bit12
bit11
bit10
bit9
bit8
bit7
bit6
bit5
bit4
bit3
bit2
bit1
bit0
00
OUT
0_DIF
OUT
1_DIF
OUT
2_DIF
OUT
3_DIF
OUT
4_DIF
OUT
5_DIF
OUT 7
OUT 6
OUT 5
OUT 4
OUT 3
OUT 2
OUT 1
OUT 0