62
7 FUNCTIONS
7.4 Error Clear Function
7.4
Error Clear Function
When an error has occurred, the error can be cleared from "System Monitor".
Clicking the [Error Clear] button in "System Monitor" clears the latest error code stored in Latest error code (Un\G100) and
turns off the ERR. LED. This action is the same action as the one to be taken when errors are cleared with Error clear request
(YF) or the display unit.
When Clear setting of error history (Un\G8002) has been set to Clear the history. (1), the error history is also cleared.
For how to clear errors with Error clear request (YF) or the display unit, refer to the following.
Page 246 Error clear request (YF)