8 FUNCTIONS OF THE CONFIGURATION TOOL
8.10 Debug Function
99
8
4.
Click "Writing to Module" to write the simulation input data into the flexible high-speed I/O control module.
If a communication error has occurred during the communication with the module with the simulation function,
the possible cause is one of the following causes. Check the target module and communication status.
• A module with the target start I/O number does not exist.
• A communication error has occurred during online access.
• Cable error
5.
Click "Simulation run" to execute the simulation of the written simulation input data.
The simulation is executed by using the hardware logic and simulation input data written into the module. When the simulation
input data has been edited, always press the "Write to Module" button to write the data into the module in advance.
• If the simulation is started during a hardware logic control, the hardware logic control will stop. After the
completion of the simulation, the stop status of the hardware logic control will continue. To start the
hardware logic control after the simulation, turn on Hardware logic control start request (Y4).
• If Hardware logic control start request (Y4) or Hardware logic control stop request (Y5) is turned on during
the simulation, simulation execution results cannot be properly acquired.
• If Hardware logic control start request (Y4) is turned on while simulation execution results are being
acquired after the simulation, the acquisition of the simulation execution results will stop.
6.
Save the simulation execution results. (Data is saved only in the CSV format.)
7.
The simulation execution results can be visually checked with GX LogViewer.
For details on GX LogViewer, refer to the following.
GX LogViewer Version 1 Operating Manual