6 INSTALLATION AND EXTERNAL WIRING
6.2 External Wiring
■
Example of noise reduction measures taken to shielded cables
■
Assembling the A6CON1
(1)
Remove the jacket of each shielded cable.
(2)
Take out a shield from a shielded cable and solder it on the FG wire.
(3)
Connect a shield of each shielded cable with a conductive tape.
(4)
Cover a connector pin with a heat-shrinkable insulation tube to protect signal wires. If signal wires are bared, the module may be affected by static
electricity and malfunction.
(5)
Cover the signal wires with an insulating tape.
(1)
Cover the cables on which a conductive tape has been applied with a heat-shrinkable tube.
(5)
(4)
(2)
(1), (3)