Appendix 5 List of Link Special Register (SW)
SW0052
System link startup
result
Stores the results when data link is started by 'System link startup' (SB0002).
0: Normal
1 or greater: Error definition in own station (Error code is stored.)
When 'System link startup' (SB0002) is turned off, the stored error definition is
cleared.
(Conditions)
• This register is enabled when 'Baton pass status of own station' (SB0047) is off.
• When 'Baton pass status of own station' (SB0047) is turned on (error), data prior
to error is held.
(Master
operating
station only)
SW0053
System link stop result
Stores the results when data link is stopped by 'System link stop' (SB0003).
0: Normal
1 or greater: Error definition in own station (Error code is stored.)
When 'System link stop' (SB0003) is turned off, the stored error definition is cleared.
(Conditions)
• This register is enabled when 'Baton pass status of own station' (SB0047) is off.
• When 'Baton pass status of own station' (SB0047) is turned on (error), data prior
to error is held.
(Master
operating
station only)
SW0054
Temporary error invalid
station setting result
Stores the results when executing the temporary error invalid station setting by
'Temporary error invalid station setting request' (SB0010).
0: Normal
1 or greater: Error definition (Error code is stored.)
When 'Temporary error invalid station setting request' (SB0010) is turned off, the
stored error definition is cleared.
(Master
operating
station only)
SW0055
Temporary error invalid
station setting cancel
result
Stores the results when canceling the temporary error invalid station setting by
'Temporary error invalid station setting cancel request' (SB0011).
0: Normal
1 or greater: Error definition (Error code is stored.)
When 'Temporary error invalid station setting cancel request' (SB0011) is turned off,
the stored error definition is cleared.
(Master
operating
station only)
SW0056
Result of reserved
station function disable
request
Stores the results when disabling the reserved station function by 'Reserved station
function disable request' (SB0012).
0: Normal
1 or greater: Error definition (Error code is stored.)
When 'Reserved station function disable request' (SB0012) is turned off, the stored
error definition is cleared.
(Master
operating
station only)
SW0057
Result of reserved
station function enable
request
Stores the results when reserved station function disable is undone by 'Reserved
station specification enable request' (SB0013).
0: Normal
1 or greater: Error definition (Error code is stored.)
When 'Reserved station specification enable request' (SB0013) is turned off, the
stored error definition is cleared.
(Master
operating
station only)
SW0058
Total number of slave
stations setting value
Stores the total number of slave stations that are set by the parameters.
Range: 1 to 120
SW0059
Total number of slave
stations present value
Stores the total number of slave stations that are actually connected by data link.
Range: 1 to 120 (0 when own station is disconnected)
SW005A
Maximum baton pass
station number
Stores the maximum station number of the stations where the baton pass is
normally performed.
Range: 1 to 120 (0 when own station is disconnected)
(Conditions)
• This register is enabled when 'Baton pass status of own station' (SB0047) is off.
• When 'Baton pass status of own station' (SB0047) is turned on (error), data prior
to error is held.
SW005B
Maximum data link
station number
Stores the maximum station number of the station where the data link is normally
performed.
Range: 1 to 120 (0 when own station is disconnected)
(Conditions)
• This register is enabled when 'Data link error status of own station' (SB0049) is
off.
SW005C
Forced master switching
command result
Stores the execution result of 'Forced master switching command' (SB0019).
0: Normal
1 or greater: Error definition (Error code is stored.)
(Submaster
station only)
No.
Name
Description
Availability
Master
station
(submaster
station)
Local
station
Содержание MELSEC iQ-R04ENCPU
Страница 2: ......
Страница 61: ...1 FUNCTIONS 1 3 IP Packet Transfer Function 59 1 ...
Страница 385: ...383 I Transient transmission 15 ...
Страница 389: ......