4 TROUBLESHOOTING
4.7 Event List
00C02
Response error from/to another station
• Abnormal response was returned from another station when accessing
another station.
• Abnormal response was returned to another station when accessed from
another station.
00C10
<<Own station>> Data link stop (cyclic transmission
stopped)
Data link of the own station was stopped.
00C11
<<Another station>> Data link stop (cyclic transmission
stopped)
Data link of another station was stopped.
00C20
<<Another station>> Parameter error occurrence
An parameter error has occurred in another station.
00C21
<<Another station>> Error occurrence
An error has occurred in another station.
00C22
Station already in use
Master station/submaster station duplication, or station number overlap has
occurred in the network.
00C23
Loopback occurrence
Path switching has occurred when using a ring topology (using the loopback
function).
00C24
<<Another station>> Receive frame error occurrence
A receive frame error has occurred at another station.
00C25
Receive parameter error occurrence
A parameter error received from the master station or control station has been
detected.
00C27
Transient reception failed
Frequency of transient transmission to the own station is too high and transient
reception failed.
00C28
<<Own station>> Receive frame error line status warning
level
A receive frame error (line status: warning level) has been occurred.
00C29
<<Another station>> Receive frame error line status
warning level
A receive frame error (line status: warning level) has been occurred.
Event code
Overview
Cause