3 PROGRAMMING
3.5 Communication Example of Safety Communication Function Used in a Redundant Line
203
3
Intelligent device station setting
Connect the engineering tool to the remote head module of the remote head module No.1, and set parameters.
In a system using the SIL2 Process CPU, write the same parameters also to remote head module No.2.
1.
In the following window, set the remote head module.
2.
In the following window, set the items for Base/Power/Extension Cable Setting.
[Navigation window]
[Parameter]
[System Parameter]
[I/O Assignment] tab
[Base/Power/Extension Cable
Setting]
3.
In the I/O assignment setting, set the remote head module No.2 for slot No.0.
[Navigation window]
[Parameter]
[System Parameter]
[I/O Assignment] tab
[I/O Assignment Setting]
4.
In the I/O assignment setting, set the I/O module with diagnostic functions to be mounted.