4 TROUBLESHOOTING
4.5 List of Error Codes
3007H
Pairing is set to the stations not included in a
redundant system.
Check the pairing setting in "Network Configuration
Settings" under "Basic Settings" of the master station.
Parameter information
• Parameter type
• I/O No.
• Parameter No.
• Network No.
• Station No.
3008H
• "RJ71GF11-T2" is selected for the module name in
a redundant system.
• "RJ71GF11-T2 (MR)", "RJ71GF11-T2 (SR)", or
"RJ71GF11-T2 (LR)" is selected for the module
name in a system other than a redundant system.
• When using the module in a redundant system,
select "RJ71GF11-T2 (MR)", "RJ71GF11-T2 (SR)",
or "RJ71GF11-T2 (LR)" for the module name in the
"Add New Module" window.
• When using the module in a system other than a
redundant system, select "RJ71GF11-T2" for the
module name in the "Add New Module" window.
Parameter information
• Parameter type
• I/O No.
• Parameter No.
• Network No.
• Station No.
3040H
Response data of the dedicated instruction cannot be
created.
• Increase the request interval.
• Decrease the number of request nodes.
• Wait for a response to the previous request before
sending the next request.
• Correct the timeout value.
3600H
The inter-module synchronization cycle setting does
not match the master station setting.
Correct the parameter so that all modules performing
inter-module synchronization have the same
frequency setting.
Parameter information
• Parameter storage
location
• Parameter type
• I/O No.
• Parameter No.
3601H
"Network Synchronous Communication" in "Network
Configuration Settings" under "Basic Settings" of the
master station does not match the inter-module
synchronization target module of the own station.
Check the network configuration setting and check if
inter-module synchronization is set.
Parameter information
• Parameter storage
location
• Parameter type
• I/O No.
• Parameter No.
3602H
Inter-module synchronization cycle failure occurred
between networks.
• Check the network status using the CC-Link IE Field
Network diagnostics of the engineering tool, and
take action.
• Check if the switching hub and the cables are
connected properly.
• If the request source is on another network, check if
the routing parameters are set correctly, and take
action.
• If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
3C00H to
3C03H
A hardware failure has been detected.
• Take measures to reduce noise.
• Reset the CPU module, and run it again. If the error
occurs again even after taking the above, the
possible cause is a hardware failure of the module,
base unit, or extension cable. Please consult your
local Mitsubishi representative.
3C0FH to
3C11H
A hardware failure has been detected.
• Take measures to reduce noise.
• Reset the CPU module, and run it again. If the error
occurs again even after taking the above, the
possible cause is a hardware failure of the module,
base unit, or extension cable. Please consult your
local Mitsubishi representative.
3C14H
A hardware failure has been detected.
Reset the CPU module, and run it again. If the error
occurs again even after taking the above, the possible
cause is a hardware failure of the error module or
CPU module. Please consult your local Mitsubishi
representative.
3C2FH
An error was detected in the memory.
Reset the CPU module, and run it again. If the error
occurs again even after taking the above, the possible
cause is a hardware failure of the error module.
Please consult your local Mitsubishi representative.
3E00H
An error was detected in the network module.
Reset the CPU module, and run it again. If the error
occurs again even after taking the above, the possible
cause is a hardware failure of the error module.
Please consult your local Mitsubishi representative.
Error
code
Error details and causes
Action
Detailed Information