3 PROGRAMMING
3.5 Communication Example of Safety Communication Function Used in a Redundant Line
211
3
21.
Set the redundant function module of the own system as the system A in the "System A/B Setting" window, and reset the
CPU modules of both systems or power off and on the both systems.
[Online]
[Redundant PLC Operation]
[System A/B Setting]
22.
Log on to the programmable controller.
[Online]
[User Authentication]
[Log on to PLC]
If logon cannot be performed, writing user information or initializing all information of the programmable controller is
required. (
GX Works3 Operating Manual)
23.
Write the set parameters to the system A CPU module.
[Online]
[Write to PLC]
24.
Click the [Yes] button to write to the CPU modules of both systems.
25.
Either reset the CPU modules of both systems or power off and on both systems.
In this setting example, default settings are used for parameters that are not shown above. For the parameter
setting, refer to the following. (