4 TROUBLESHOOTING
4.5 List of Error Codes
259
4
3000H
Any of following items are set in the module which is
set as a target in "Inter-module Synchronous Setting"
in the [Inter-module Synchronous Setting] tab of the
"System Parameter" window.
• "Setting Method" under "Station No." in "Required
Settings" is set to "Program".
• "Setting Method of Basic/Application Settings"
under "Parameter Setting Method" in "Required
Settings" is set to "Program".
• "Station Type" under "Station Type" in "Required
Settings" is set to "Submaster Station".
• "Network Topology" in "Basic Settings" is set to
"Ring".
• "Link Scan Mode" under "Supplementary Cyclic
Settings" in "Application Settings" is set to "Constant
Link Scan" or "Sequence Scan Synchronous
Setting".
• A station in which "Station Type" is set to
"Submaster station" is set in "Network Configuration
Settings" of "Basic Settings".
Correct parameter shown in cause.
Parameter information
• Parameter type
• I/O No.
• Parameter No.
Although a slave station in which "Network
Synchronous Communication" in "Network
Configuration Settings" of "Basic Settings" is set to
"Synchronous" exists, the system parameter and
control CPU are in the any of following states.
• The master/local module is not set as the target
module in "Inter-module Synchronous Setting" in the
[Inter-module Synchronous Setting] tab of the
"System Parameter" window.
• The control CPU is a CPU module in which the inter-
module synchronization function cannot be used.
3001H
• A station with the same station number was found in
the same network.
• Multiple master stations and submaster stations
were detected in the same network.
Correct the station number or station type of the
station where the error was detected.
After taking the above actions, power off and on or
reset all stations where the error was detected.
Parameter information
• Parameter type
• I/O No.
• Parameter No.
A station of CC-Link IE Controller Network (Ethernet
cable) was found in the same network.
Divide it into CC-Link IE Controller Network (Ethernet
cable) and the network.
After taking the above actions, power off and on or
reset all stations where the error was detected.
3004H
The number of points set in "RWw/RWr Setting" for the
remote device station (safety station) is less than 16 in
"Network Configuration Settings" of "Basic Settings".
Set "RWw/RWr Setting" for the remote device station
(safety station) to 16 points in "Network Configuration
Settings" of "Basic Settings".
Parameter information
• Parameter type
• I/O No.
• Parameter No.
• Network No.
• Station No.
3005H
Parameters for the master station and submaster
station do not match.
Match the following parameters for the master station
and submaster station.
• "Network Configuration Settings" in "Basic Settings"
• "Network Topology" in "Basic Settings"
• "Link Scan Mode" under "Supplementary Cyclic
Settings" in "Application Settings"
• "Constant Link Scan Time" of "Link Scan Mode"
under "Supplementary Cyclic Settings" in
"Application Settings"
• "Station-based Block Data Assurance" under
"Supplementary Cyclic Settings" in "Application
Settings"
• "IP Address" in "Application Settings"
• "Communication Mode" in "Application Settings"
• "Redundant System Settings" in "Application
Settings"
Parameter information
• Parameter type
• I/O No.
• Parameter No.
• Network No.
• Station No.
3006H
Pairing is not set to the stations in a redundant system.
Check the pairing setting in "Network Configuration
Settings" under "Basic Settings" of the master station.
Parameter information
• Parameter type
• I/O No.
• Parameter No.
• Network No.
• Station No.
Error
code
Error details and causes
Action
Detailed Information