1 FUNCTIONS
1.8 Safety Communication Function
117
1
■
Precautions
• This function may detect an error and stop safety communications if the network is reconnected in all the stations during
safety communications. For reconnection of the network, refer to the section explaining the redundant system function.
(
Page 79 Redundant System Function)
• A safety connection with the intelligent device station (safety station) can be established only while data link is performed
after configuring the "Safety Communication Setting" under "Application Settings" of the master station. The data link status
can be checked in 'Redundant system data link status of each station' (SW01B0 to SW01B7).
• Note that stations not set in "Network Configuration Settings" under "Basic Settings" of the master station (safety station)
and reserved stations cannot establish a safety connection.
• When the momentary power failure occurs on the intelligent device station (safety station) during safety communications,
safety communications may stop. (
MELSEC iQ-R CC-Link IE Field Network Remote Head Module User's Manual
(Application))